A.1 Power Ratings
u
Three-Phase 600 V Class Drive Models 5A0125 to 5A0242
Drive Models
Maximum Applicable Motor Capacity (HP)
Input Current (A)
Input
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
Input Power (kVA)
Rated Output Capacity (kVA)
Rated Output Current (A)
Output
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency default setting is Swing PWM 1 (C6-02 = 7). C6-02 settings 1, 7, 8, 9, and A do not require current derating. All other settings
raise the carrier frequency and require current derating.
324
Table A.9 Power Ratings Continued (Three-Phase 600 V Class)
Item
<1>
ND Rating
<2>
ND Rating
Rated Voltage
Rated Frequency
ND Rating
ND Rating
<3>
ND Rating
Overload Tolerance
Carrier Frequency
5A0125
125
129
Three-phase 500 to 600 Vac 50/60 Hz
147
124
<4>
125
<4>
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
User-adjustable between 1 and 3 kHz
Three-phase 500 to 600 V (proportional to input voltage)
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Specification
5A0145
5A0192
150
200
158
228
-10 (-15) to +10%
±5%
181
261
144
191
145
192
400 Hz (user-set)
5A0242
250
263
301
241
242
<4>