YASKAWA iQpump1000 User Manual page 8

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

Step
iQpump Factory Defaults Overview
7
(adjust certain settings specific to the application)
No.
Value
Description
b5-03
3.0 sec.
PI Integral Time
PI Feedback Ref-
2
erence Missing
b5-12
(Fault)
Detection Selec-
tion
20.0 sec.
Acceleration Time
C1-01
See Note
1
10.0 sec.
Deceleration
C1-02
See Note
Time 1
Number of Re-
L5-01
5
start Attempts
Maximum Restart
L5-03
20 sec.
Time After Fault
Minimum Pump
P1-06
40.0 Hz
Frequency
P2-03
5 sec.
Sleep Delay Time
Thrust Bearing
P4-12
30.0 Hz
Frequency
P4-17
0.2 Min
Utility Start Delay
1
SYSTEM FEEDBACK UNIT /
FEEDBACK DEVICE SCALING
P1-02 Feedback Unit
0: Inch of Water
8: Bar
1: PSI
9: Pascal
2: GPM
10: Degrees Celsius
3: Degrees Fahrenheit
11: Meter
4: CFM
12: Feet
5: CMH
13: Liters per Minute
6: Liters / Hr
14: cm per Minute
7: Liters/Sec
15: Inch Hg
25: No Unit
P1-03 = 200.0 PSI Feedback Scaling
Feedback
Maximum
8
Reference
Decrease integral time to make iQpump more responsive.
Select what to do when the feedback device (transducer) fails or gets disconnected.
0: Disabled, continue running no message is displayed
1: Alarm, show warning on the keypad when the feedback device fails or is discon-
nected
2: Fault, stop pump system when the feedback fails or is disconnected
Time it takes to accelerate the pump motor from zero to maximum speed.
NOTE: Factory default with Thrust Mode enabled is 12.0 sec, 20.0 sec when dis-
abled.
Time it takes to decelerate the pump motor from maximum speed to zero.
NOTE: Factory default with Thrust Mode enabled is 5.0 sec, 10.0 sec when dis-
abled.
Determines the number of times iQpump will perform an automatic restart on the
faults listed in the comments column.
iQpump System Protection Faults that can be setup to restart are Low Level Feed-
back,
High Level Feedback, Transducer Loss, Not Maintaining Setpoint, Loss of Prime,
Pump Over Cycle. Refer to parameters P4-07 and P4-08. The number of restart at-
tempts is set by L5-01.
If the restart fails (or is not attempted due to a continuing fault condition) iQpump
waits the Maximum Restart Time After Fault, before attempting another restart.
Minimum speed (Hz) the pump motor has to operate at.
Example: Base pump motor speed is 3600 RPM, minimum speed is 2400 RPM. Set
minimum pump frequency to 40.0 Hz. (2400 ÷ 3600 x 60 Hz = 40 Hz)
Time it takes before the pump system goes to sleep when the selected signal level
(P2-01) falls below the specified sleep level (P2-02)
Sets the frequency reference used when the thrust bearing function is active. A
value of 0 disables this function.
When utility power is restored and P4-10 is enabled (1), iQpump waits the time
specified in P4-11 before auto operation becomes active.
2
START / DRAW DOWN LEVEL
Example: Absolute Level (Positive Start Level)
SYSTEM STARTS WHEN
200
Start Level Delay (P1-05)
PRESSURE SIGNAL FALLS
PSI
(Example 5.0 sec.)
BELOW 100 PSI
150
Feedback Signal from pressure
transducer (4 – 20 mA)
Start
Start Pump System
WAIT
0
Delay
Time
System Setpoint
Feedback Scaling (P1-03)
(Example 150.0 PSI)
(Example 200.0 PSI)
System Units (P1-02)
Start / Draw Down Level (P1-04)
(Example PSI)
(Example 100.0 PSI)
START / DRAW DOWN LEVEL
Example: Delta Level (Negative Start Level)
200
Start Level Delay (P1-05)
PSI
(Example 5.0 sec.)
150
WAIT
Delay
System Setpoint
(Example 150.0 PSI)
System Units (P1-02)
(Example PSI)
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Comments
Caution: can cause instability if
value is too low.
NOTE: Disable parameter b5-12
if no transducer is installed.
Adjusted depending on system
performance
Overcurrent
Ground Fault
Output Phase Loss
Input Phase Loss
iQpump Overload
Motor Overload
Overtorque
DC Bus Fuse Blown
DC Bus Undervoltage
DC Bus Overvoltage
Overheat
P1-06 should be set to the level
where the pump can produce the
minimum pressure even at zero
flow.
Adjust according to system
requirements.
Primarily used for submersible
pumps. Program P4-12 = 0.0 Hz
to disable function when iQpump is
used with a centrifugal pump.
Note: Only active when P4-10 is
enabled (1) and operation
(start/stop) is from the
digital operator.
SYSTEM STARTS WHEN
PRESSURE SIGNAL FALLS
BELOW 100 PSI
-50.0 PSI
Feedback Signal from pressure
transducer (4 – 20 mA)
Start
Start Pump System
Time
Feedback Scaling (P1-03)
(Example 200.0 PSI)
Start / Draw Down Level (P1-04)
(Example -50.0 PSI, (150.0 – 50.0)