D.2 UL and CSA Standards
D.2 UL and CSA Standards
u
UL Standards Compliance
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing and
evaluation, and determined that their stringent standards for product safety have been met. For a product to receive UL
certification, all components inside that product must also receive UL certification.
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions described
below must be met to maintain compliance when using this drive in combination with other equipment:
n
Installation Area
Do not install the drive to an area greater than pollution degree 2 (UL standard).
n
Main Circuit Terminal Wiring
Yaskawa recommends using closed-loop crimp terminals on all drive models. To maintain UL/cUL approval, UL Listed
closed-loop crimp terminals are specifically required when wiring the drive main circuit terminals on models 2A0110 to
2A0415, 4A0058 to 4A1200, and 5A0041 to 5A0242. Use only the tools recommended by the terminal manufacturer for
crimping.
Refer to Closed-Loop Crimp Terminal Size on page 496
Closed-Loop Crimp Terminal Recommendations
To maintain UL/cUL approval, UL Listed closed-loop crimp terminals are specifically required when wiring the drive main
circuit terminals on models 2A0110 to 2A0415, 4A0058 to 4A1200, and 5A0041 to 5A0242. Use only the tools recommended
by the terminal manufacturer for crimping. Yaskawa recommends crimp terminals made by JST and Tokyo DIP (or equivalent)
for the insulation cap.
Table D.4
terminals, tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge
and screw size for your drive model. Place orders with a Yaskawa representative or the Yaskawa sales department.
Wire gauge values shown in bold italic are the recommended values. Refer to local codes for proper selections.
Wire Gauge (AWG, kcmil)
Drive Model
R/L1, S/L2, T/L3
2A0004
2A0006
2A0008
2A0010
14
2A0012
12
2A0018
2A0021
2A0030
496
Figure D.6 UL/cUL Mark
matches the wire gauges and terminal screw sizes with Yaskawa-recommended crimp
Table D.4 Closed-Loop Crimp Terminal Size
Screw
Size
U/T1, V/T2, W/T3
14
12
M4
10
14
12
M4
10
14
12
M4
10
12
M4
10
10
8
M4
6
for closed-loop crimp terminal recommendations.
Crimp
Tool
Terminal
Model
Machine No.
Number
200 V Class
R2-4
YA-4
R5.5-4
R2-4
YA-4
R5.5-4
R2-4
YA-4
R5.5-4
R5.5-4
YA-4
R5.5-4
8-4
YA-4
14-NK4
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Insulation
Cap Model
Die Jaw
No.
TP-003
AD-900
TP-005
TP-003
AD-900
TP-005
TP-003
AD-900
TP-005
AD-900
TP-005
AD-900
TP-005
AD-901
TP-008
AD-902
TP-014
<1>
Code
100-054-028
100-054-029
100-054-028
100-054-029
100-054-028
100-054-029
100-054-029
100-054-029
100-054-031
100-054-033