YASKAWA iQpump1000 User Manual page 411

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
P4-24
(0D11) Low City Alarm Text
P4-25
Remote Drive Disable
(0D12)
Selection
P4-26
(0D13) Remote Drive Disable
On-Delay
P4-27
(0D14) Remote Drive Disable
Off-Delay
P4-29
Lube Pump Message
(0D16)
Text
<4>
P4-30
Lube Pump Active
(0D17)
During Run
<4>
P4-31
(0D18) Lube Pump / Digital
Output Delay Timer
P4-32
(0D19)
Pre-charge Level 2
<4>
P4-36
(0D1D)
Pressure Reached Exit
Conditions
<6>
P4-37
(0D1E)
Pressure Reached
Hysteresis Level
<6>
P4-38
(0D1F)
Pressure Reached On-
Delay Time
<6>
P4-39
(0D20)
Pressure Reached Off-
Delay Time
<6>
P4-40
(0D21)
Pressure Reached
Detection Selection
<6>
<1> Unit is determined by P1-02, System Units, setting.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
LCD Display
Selects the alarm message that will be displayed when a Low
Low City Alarm Txt
City Pressure condition is detected.
0: Low Cty Pressure
0: Low city pressure
1: Low Suction Pres
1: Low suction pressure
2: Low Watr in Tank
2: Low water in tank
Selects the type of pressure switch connected to the "Remote
Drive Disable" digital input (H1-0o = 95).
Rem Drv Dis Sel
0: Normally open (closed indicates the Remote Drive Disable
0: Normally Open
condition)
1: Normally Closed
1: Normally closed (open indicates the Remote Drive Disable
condition)
Sets the amount of time a Remote Drive Disable condition must
be present before the drive will stop.
Drv Dis On-Delay
Sets the amount of time a Remote Drive Disable condition must
be absent before the drive will run.
Drv Dis OffDelay
Selects which text is displayed when Lube Pump is active. Also
changes the text for the Lube Pump Digital Output selection
Lube Pump MsgText
(H2-oo = 8B)
0: Lube Pump
0: Lube Pump
1: DigitalOut Delay
1: Digital Out Delay
2: Primer Pump
3: SreenMtrStarter
2: Primer Pump
3: Screen Motor Starter
When enabled, the Lube Pump digital output stays activated
Lube Pump DurRun
after the timer expires and the drive starts to run normally. The
0: Disabled
output is deactivated only when the drive stops, faults, or sleeps.
1: Active DuringRun
0: Disabled
1: Active During Run
Sets the amount of time to delay the drive output and to energize
the digital output (H2-oo = 8B) before the drive is allowed to
Lube Pump Time
run.
Setting this parameter to 0.0 disables the function.
For normal PI operation during Pre-charge 2, if the PI Feedback
signal rises above the P4-32 level, Pre-charge 2 is cancelled and
the drive resumes normal operation.
For inverse PI operation and during Pre-charge 2, if the PI
PreCharge Level2
Feedback signal goes below the P4-32 level, Pre-charge 2 is
cancelled and the drive resumes normal operation.
When set to zero, Pre-charge 2 still runs when P4-07 is set, but
uses P4-01 to determine if normal operation should resume.
Pressure Reached
Determines Selects how the digital output reacts to Feedback
0: Hyst Above
changes after it activates.
&Below
0: Hysteresis Above and Below
1: Hysteresis 1-Way
1: Hysteresis One Way
Sets the hysteresis level for exiting the Pressure Reached
Press Reach Hyst
condition.
Sets the delay time that is applied prior to activating the Pressure
PressReach OnDly
Reached condition.
Sets the delay time that is applied prior to deactivating the
PressReachOffDly
Pressure Reached condition.
Sets the value that the drive status must match to trigger the
PressReachDetSel
Pressure Detection digital output.
0: Always
0: Always
1: Drive Running
1: Drive Running
2: Run Command
2: Run Command
Description
<6>
<6>
B.12 P: Pump Parameters
Values
Page
Default: 0
Range: 0 to 2
Default: 1
Range: 0, 1
Default: 0 s
Min.: 0
Max.: 1000
Default: 0 s
Min.: 0
Max.: 1000
Default: 0
Range: 0 to 3
Default: 0
Range: 0, 1
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<5>
Default: 0.0 PSI
<1>
Min.: 0.0
Max.: 6000.0
Default: 1
Range: 0, 1
Default: 3.0 PSI
<1>
Min.: 0.1
Max.: 100.0
Default: 1.0 s
Min.: 0.1
Max.: 60.0
Default: 1.0 s
Min.: 0.1
Max.: 60.0
Default: 0
239
Range: 0 to 2
B
411

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents