H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.
Set jumper S5 on the terminal board accordingly when changing these parameters.
Selection on page 129
for details on setting S5.
No.
H4-07
H4-08
Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Setting 2: 4 to 20 mA
n
L5-01: Number of Auto Restart Attempts
Sets the number of times that the drive may attempt to restart itself.
When the counter reaches the number set to L5-01, the operation stops and the fault must be manually cleared and reset.
The restart counter is incremented at each restart attempt, regardless of whether the attempt was successful. When the counter
reaches the number set to L5-01, the operation stops and the fault must be manually cleared and reset.
The number of fault restarts is reset to zero when:
• The drive operates normally for 10 minutes following a fault restart.
• A fault is cleared manually after protective functions are triggered.
• The power supply is cycled.
No.
L5-01
n
L5-04: Fault Reset Interval Time
Determines the amount of time to wait between restart attempts when parameter L5-05 is set to 1.
No.
L5-04
n
o1-08: Third Line User Monitor Selection
Selects the monitor that is shown in the third line. Effective only when o1-06 is set to 1.
Enter the last three digits of the monitor parameter number to be displayed: Uo-oo. For example, set "403" to display
monitor parameter U4-03.
No.
o1-08
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
H4-07, 08 = 0
Bias 30%
Gain 100%
Bias 0%
Gain 100%
100%
Monitor Value
Figure 4.45 Analog Output Gain and Bias Setting Example 3
Name
Multi-Function Analog Output Terminal FM
Signal Level Selection
Multi-Function Analog Output Terminal AM
Signal Level Selection
Name
Number of Auto Restart Attempts
Name
Fault Reset Interval Time
Name
Second Line User Monitor Selection
4.7 Basic iQpump Setup and Application Preset Parameters
Output Voltage
-100%
Gain = 100%
H4-07, 08 = 1
Bias = 30%
10V
Gain = 100%
Bias = 0%
3 V
100%
Monitor Value
-4 V
-10 V
Refer to Terminal AM/FM Signal
Setting Range
0 to 2
0 to 2
Setting Range
0 to 10 Times
Setting Range
0.5 to 600.0 s
Setting Range
101 to 799
Default
0
0
Default
5 Times
4
Default
10.0 s
Default
103