B.3 b: Application
Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions, PID
control, the Dwell function, Energy Savings, and other application-related settings.
u
b1: Operation Mode Selection
No.
(Addr.
Name
Hex)
b1-01
Frequency Reference
(0180)
Selection 1
b1-02
Run Command
(0181)
Selection 1
b1-03
Stopping Method
(0182)
Selection
b1-04
Reverse Operation
(0183)
Selection
Run Command
b1-07
Retention when Source
(0186)
is Changed
Run Command
b1-08
Selection in
(0187)
Programming Mode
b1-11
Run Delay at Stop
(01DF)
(Back Spin Timer)
b1-12
Run Delay Memory
(01E0)
Selection
<1>
b1-14
Phase Order Selection
(01C3)
b1-15
Frequency Reference
(01C4)
Selection 2
<1>
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
LCD DIsplay
Ref Source 1
0: HOA keypad
0: Operator
1: Analog input terminals
1: Analog Input
2: MEMOBUS/Modbus communications
2: Serial Com
3: Option PCB
3: Option PCB
4: Pulse input (terminal RP)
4: Pulse Input
5: Geothermal Mode (Frequency reference dependent on
5: Geothermal
temperature input (H3-0o = 21)
Run Source 1
0: HOA keypad
0: Operator
1: Digital input terminals
1: Digital Inputs
2: MEMOBUS/Modbus communications
2: Communication
3: Option PCB
3: Option PCB
6: AUTOKey + Term
6: AUTOKey + Term
7: AUTOKey + Serial
7: AUTOKey + Serial
8: AUTOKey + Option
8: AUTOKey + Option
Stopping Method
0: Ramp to stop
0: Ramp to Stop
1: Coast to stop
1: Coast to Stop
2: DC Injection Braking to stop
2: DCInj to Stop
3: Coast with timer
3: Coast w/Timer
Reverse Oper
0: Reverse enabled
0: Reverse Enabled
1: Reverse disabled
1: Reverse Disabled
Determines whether the run command is retained when the
RunCmd@SrcChange
Sequence Selection is changed
0: Require Cycle
0: Require Cycle
1: Retain Run Cmd
1: Retain Run Command
RUN dur PRG Mode
0: Run command is not accepted while in Programming Mode.
0: Run
1: Run command is accepted while in Programming Mode.
Disabled@PRG
2: Prohibit entering Programming Mode during run.
1: Run Enabled@PRG
2: Prg only @ Stop
Sets the amount of time that the drive will disallow the
reapplication of the Run command after the Run command is
lost. b1-11 is active for all b1-03 settings.
Run Delay @ Stop
If set to zero and b1-03 = 3 (Coast to Stop w/ Timer), a
combination of C1-02 and output frequency determine the
length of time. Otherwise, no run delay will be applied.
Determines whether the Run Delay Timer is saved to the
EEPROM during power loss.
0: Disabled
1: Only at Stop
2: Running & Stop
Run Dly Mem Sel
Note:
Rotation Sel
0: Standard
0: Standard
1: Switch phase order (reverses the direction of the motor)
1: SwitchPhaseOrder
Enabled when a multi-function digital input set for "External
Ref Source 2
Reference" (H1-oo = 2) closes.
0: Operator
0: Operator
1: Analog Input
1: Analog Input
2: Serial Com
2: Serial Communications
3: Option PCB
3: Option PCB
4: Pulse Input
4: Pulse Input
Description
<2>
<2>
<2>
A JVOP-183 HOA Keypad must be plugged into
the drive for settings 1 and 2 to function. If the
keypad is removed, b1-12 will function as setting
0 (Disabled).
B.3 b: Application
Values
Page
Default: 0
214
Range: 0 to 5
Default: 0
Range: 0 to 3; 6
217
to 8
Default: 1
218
Range: 0 to 3
Default: 1
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Range: 0 to 2
Default: 0.0 s
Min.: 0.0
Max.: 6000.0
Default: 2
Range: 0 to 2
Default: 0
Range: 0, 1
Default: 0
Range: 0 to 4
B
353