u
Multi-function Digital Input On/Off Time Delay
This function provides an On/Off Delay to all multi-function digital inputs.
Note:
1. This function is available in drive software versions PRG: 8552 and later.
2. Not available in drive models 4A0930 and 4A1200.
When the terminal closes, the function programmed to that terminal activates after the corresponding on-delay timer elapses.
Opening the terminal will reset the on-delay timer. When the terminal opens and the function is active, the function continues
to run until the off-delay timer elapses. Closing the terminal again will reset the off-delay timer.
The on-delay and off-delay timers also affect monitor U1-10 (Input Terminal Status). The corresponding bits are set when the
function is active after the on-delay elapses. the bits are reset when the function is deactivated after the off-delay elapses. The
on-delay timer does not apply when the inputs are already closed at power-up.
n
Related Parameters
No.
H1-37, H1-38
Terminals S7 and S8 On-Delay Time
H1-41 to H1-48
Terminals S1 to S8 Off-Delay Time
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Parameter Name
4.6 iQpump Presets and Functions
Setting Values
Default: 0.00 s
Range: 0.00 to 300.00 s
Default: 0.00 s
Range: 0.00 to 300.00 s