Setting 0: No display
Setting 1: Alarm only
Setting 2: Fault
Setting 3: Auto-restart (time set by L5-04)
n
P6-25: Flow Rate Limit Foldback Message Style
Selects how the "Flow Rate Limit Foldback" message is displayed on the operator.
No.
P6-25
Setting 0: Full Screen Message
Setting 1: Home Monitor Text
n
Q1-01: PID Controller Setpoint 1
Sets the PID setpoint for the controller. The drive will use the system feedback signal and modulate the pump speed to regulate
the feedback at the Q1-01 setpoint. The units for Q1-01 are selected by b1-01 and the scaling is set in parameter P1-03. This
parameter is active when b1-01 (Reference Source) is set to 0 (HOA keypad).
No.
Q1-01
n
Q3-06: Current Limit Foldback Message Style
Selects how the "Current Limit Foldback" message is displayed on the operator.
No.
Q3-06
Setting 0: Full Screen Message
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
4.7 Basic iQpump Setup and Application Preset Parameters
Parameter Name
Flow Rate Limit Foldback Message Style
- MODE -
Flow Rate Limit
QMONI: Use F1/F2
FlowLim Foldback
U5-99= 100PSI
U1-02= 41.50Hz
U1-91= 98.3PSI
Parameter Name
PID Controller Setpoint 1
Parameter Name
Current Limit Foldback Message Style
- MODE -
Current Limit
DRV RDY
Foldback
<- MONITOR ->
DRV RDY
Foldback
Setting Range
0, 1
Setting Range
0.0 to 6000.0
Setting Range
0, 1
Default
0
Default
0.0 PSI
Default
0
4