YASKAWA iQpump1000 User Manual page 423

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
Geothermal
Q2-09
Temperature Loss
(0E92)
Detection
Q2-10
Geothermal Sleep Delay
(0E93)
Time
Geothermal
Q2-11
Temperature Delta
(0E94)
Wake Level
Q2-12
Geothermal Sleep
(0E95)
Wake-Up Delay Time
u
Q3: Output Current Limit
No.
(Addr.
Name
Hex)
Q3-01
Output Current Limit
(0EBC)
Select
Q3-02
(0EBD) Current Limit
Q3-05
Current Limit Regulator
(0EC0)
Feedback Filter
<1>
Q3-06
Current Limit Foldback
(0EC1)
Message Style
<2>
Q3-10
Ripple Regulator
(0EC5)
Selection
Q3-11
Ripple Regulator
(0EC6)
Setpoint
Q3-13
Single Phase Foldback
(0EC8)
Message Style
<2>
<1> Available in drive software versions PRG: 8554 and later. Not available in drive models 4A0930 and 4A1200.
<2> Available in drive software versions PRG: 8553 and later. Not available in drive models 4A0930 and 4A1200.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
LCD Display
Selects the drive response when the signal from Terminal A2
falls below 3 mA or rises above 21 mA.
Geotherm Loss Det
This parameter is only effective when H3-0o = 2 (4 to 20 mA)
0: Disabled
and H3-0o = 21 (Geothermal Temperature).
1: Alarm Only
0: Disabled
2: Fault
1: Alarm
2: Fault
Set the length of time that the drive must be running at the speed
set in Q2-03, Minimum Geothermal Speed, before going to
Geotherm Slp Dly
sleep.
Sets the geothermal temperature that will wake up the drive.
The drive will wake up when one of the following conditions is
true:
Geotherm Wake Lvl
Temperature > Q2-07 + Q2-11 OR
Temperature < Q2-06 - Q2-11
Setting this parameter to 0.0 will disable Geothermal Sleep
Mode.
Sets the length of time that the setting of Q2-11, Geothermal
Temperature Delta Wake Level, must be met to wake up the
Geotherm Wake Dly
drive.
LCD Display
Current Lim Sel
Enables and disables the output current regulator.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Sets the current limit. Value is internally limited to 300% of the
drive rated current.
Current Limit
First order filter time on the feedback used for Current Limit
Feedback Filter
control.
Selects how the "Current Limit Foldback" message is displayed
Current Lim Msg
on the operator.
0: Full Screen Msg
0: Full Screen Message
1: Home Mon Text
1: Home Monitor Text
1-Phase Foldback
Enables and disables the single phase ripple regulator.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Set as a percentage of the maximum amount of ripple allowed
Ripple Reg S.P.
before triggering an input phase loss fault.
Selects how the "Single Phase Foldback" message is displayed
1Ph Foldback Msg
on the operator.
0: Full Screen Msg
0: Full Screen Message
1: Home Mon Text
1: Home Monitor Text
B.13 Q: PID Controller Parameters
Description
Description
Values
Page
Default: 1
Range: 0 to 2
Default: 30 s
Min.: 0
Max.: 3600
Default: 0.0 °F
Min.: 0.0
Max.: 50.0
Default: 5 s
Min.: 0
Max.: 3600
Values
Page
Default: 0
Range: 0, 1
Default: 0.0 A
Min.: 0.0
Max.: 1000.0
Default: 1000 ms
Min.: 5
Max.: 10000
Default: 0
241
Range: 0, 1
Default: 1
Range: 0, 1
Default: 95.0%
Min.: 0.0
Max.: 200.0
Default: 0
242
Range: 0, 1
B