5.2 Fault Detection
HOA Keypad Display
oFA00
Cause
The option card installed into port CN5-A
is incompatible with the drive
HOA Keypad Display
oFA01
Cause
The option card connection to port CN5-A
is faulty
HOA Keypad Display
oFA03 to oFA06
oFA10, oFA11
oFA12 to oFA17
oFA30 to oFA43
Cause
Option card or hardware is damaged
HOA Keypad Display
oFb00
Cause
The option card installed into port CN5-B
is incompatible with the drive
A communication option card has been
installed in option port CN5-B
HOA Keypad Display
oFb01
Cause
The option card connection to port CN5-B
is faulty
HOA Keypad Display
oFb02
Cause
An option card of the same type is already
installed in option port CN5-A
An input option card is already installed in
option port CN5-A
HOA Keypad Display
oFb03 to oFb11
oFb12 to oFb17
260
Option Card Connection Error at Option Port CN5-A
Option compatibility error
Check if the drive supports the option card to be installed. Contact Yaskawa for assistance.
Option Card Fault at Option Port CN5-A
Option not properly connected
• Turn off the power and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
• If the option is not a communication option card, try to use the card in a different option port. If the option
card works properly in a different option port, CN5-A is damaged, and the drive requires replacement. If
the error persists (oFb01 or oFC01 occur), replace the option card.
Option Card Error Occurred at Option Port CN5-A
Option Card Connection Error (CN5-A)
Communication Option Card Connection Error (CN5-A)
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Option Card Fault at Option Port CN5-B
Option compatibility error
Make sure the drive supports the option card to be installed. Contact Yaskawa for assistance.
Communication option cards are only supported by option port CN5-A. It is not possible to install more than
one communication option.
Option Card Fault at Option Port CN5-B
Option not properly connected
• Turn off the power and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
• Try to use the card in a different option port. If the option card works properly in a different option port,
CN5-B is damaged, and the drive requires replacement. If the error persists (oFA01 or oFC01 occur),
replace the option card.
Option Card Fault at Option Port CN5-B
Same type of option card is currently connected
Only one of each option card type can only be installed simultaneously. Make sure only one type of option
card is connected.
Install a communication option. More than one of the same type of card cannot be installed simultaneously.
Option card error occurred at Option Port CN5-B
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents