If the drive should follow an "Auto Set-Point" set by the HOA keypad: Set b1-01 to "0: Operator" (factory default). The Auto
setpoint can then be entered into the U1-01 monitor parameter in the "-DRIVE-" menu.
Setting 0: Operator (HOA keypad)
Using this setting, the frequency reference can be input by:
• switching between the multi-speed references in the d1-oo parameters.
• entering the frequency reference on the operator keypad.
This selection will also switch PID setpoint to Q1-01.
Setting 1: Terminals (analog input terminals)
Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1, A2, or A3.
To set the drive to follow an "Auto Setpoint" set by the analog input, set b1-01 to 1 (Terminals) and connect a potentiometer
or external signal to the drive.
Note:
When b1-01 is set to 1 (Terminals) and P5-01 is set to 0 (HAND Mode Reference), the setpoint and the HAND reference are determined
by the external analog signal.
Voltage Input
Voltage input can be used at any of the three analog input terminals. Make the settings as described in
used.
Table 4.18 Analog Input Settings for Frequency Reference Using Voltage Signals
Terminal
Signal Level
0 to 10 Vdc
A1
0 to 10 Vdc
Bipolar
0 to 10 Vdc
A2
0 to 10 Vdc
Bipolar
0 to 10 Vdc
A3
0 to 10 Vdc
Bipolar
0 to 10 V
2 k
Figure 4.33 Setting the Frequency Reference as a Voltage Signal at Terminal A1
Current Input
Input terminals, A1, A2, and A3 can accept a current input signal. Refer to
current input.
Table 4.19 Analog Input Settings for Frequency Reference Using a Current Signal
Signal
Terminal
Level
4 to 20 mA
A2
0 to 20 mA
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Signal Level
Function Selection
Selection
H3-01 = 0
(Frequency Reference Bias)
H3-01 = 1
H3-09 = 0
(Frequency Reference Bias)
H3-09 = 1
H3-05 = 0
(Frequency Reference Bias)
H3-05 = 1
Drive
+V 10.5 V, 20 mA power supply
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
Parameter Settings
Signal Level
Function
Selection
Selection
H3-09 = 2
H3-10 = 0
(Frequency Bias)
H3-09 = 3
4.7 Basic iQpump Setup and Application Preset Parameters
Parameter Settings
Gain
H3-02 = 0
H3-03
H3-10 = 0
H3-11
H3-06 = 0
H3-07
+10 V
4 k
Customer
+/- 10 V
Supply
OR
0 V
Common
Table 4.19
Gain
H3-11
Table 4.18
Bias
H3-04
Set jumper S1 on the terminal
H3-12
board to "V" for voltage input.
Set DIP switch S4 on the
H3-08
terminal board to "AI".
Drive
+V 10.5 V, 20 mA power supply
0 to 10 V
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
for an example to set terminal A2 for
Bias
Make sure to set jumper S1 on the
H3-12
terminal board to "I" for current
input.
for the input
Notes
4
Notes
215