B.2 A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
u
A1: Initialization
No.
(Addr.
Name
Hex)
A1-00
(0100)
Language Selection
<1>
A1-01
(0101)
Access Level Selection
<2>
A1-02
Control Method Selection
(0102)
A1-03
Initialize Parameters
(0103)
A1-04
Password
(0104)
A1-05
Password Setting
(0105)
A1-06
Application Preset
(0127)
A1-08
<3>
Custom Initialize Modes
(0F00)
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting value is dependent on the Initialization parameter A1-03.
<3> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
<4> Available in drive software versions PRG: 8553 and later. Not available in drive models 4A0930 and 4A1200.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
LCD Display
Select Language
0: English
0: English
1: Japanese
1:
(Japanese)
2: German
2: Deutsch
3: French
4: Italian
3: Français
5: Spanish
4: Italiano
6: Portuguese
5: Español
6: Português
0: View and set A1-01 and A1-04. Uo-oo parameters can also
Access Level
be viewed.
0: Operation Only
1: User Parameters (access to parameters selected by the user,
1: User Parameters
A2-01 to A2-32)
2: Advanced Level
2: Advanced Access (access to view and set all parameters)
3: Lock parameters
3: Lock parameters
Control Method
0: V/f Control
0: V/f Control
2: Open Loop Vector Control
2: Open Loop Vector
0: No initialization
1110: User Initialize (parameter values must be stored using
Init Parameters
parameter o2-03)
0: No Initialize
2220: 2-Wire initialization
1110: User Initialize
3330: 3-Wire initialization
2220: 2-Wire Initial
5550: Terminal->Control Initialize
3330: 3-Wire Initial
6008: Pressure Control
5550: Term->Cntrl Int
6009: Pump down level
6008: Pressure Control
6010: Geothermal mode
6009: Pump down level
6011: VTC pressure control
6010: Geothermal
mode
6012: Pivot Panel VTC
6011: VTC Pressure Ctl
6013: Advanced Pressure Control
6012: Pivot Panel VTC
6014: Pivot Panel Submersible
6013: Adv PressureCtrl
7770: General purpose
6014: Pivot Panel Sub
7771: Submersible Motor General Purpose
7770: General purpose
7771: Sub Mtr GP Oper
Note:
When the value set into A1-04 does not match the value set into
Enter Password
A1-05, parameters A1-01 through A1-03 and A2-01 through A2-33
cannot be changed.
Select Password
Note:
Application Sel
0: Pressure Control
0: Pressure Control
1: General Purpose
1: General Purpose
2: Sub Mtr GP Oper
2: Sub Mtr GP Oper
5: General Ext HOA
5: General Ext HOA
6: General HOA Keys
6: General HOA Keys
8: Pressure Control
8: Pressure Control
9: Pump Down Level
9: Pump Down Level
10: Geothermal Mode
11: VTC Pressure Ctl
10: Geothermal Mode
11: VTC Pressure Ctl
12: Pivot Panel VTC
12: Pivot Panel VTC
13: Adv PressureCtrl
13: Adv PressureCtrl
14: Pivot Panel Sub
14: Pivot Panel Sub
Custom InitModes
0: No Initialize
0: No Initialization
3005: General Ext HOA
3005: General Ext HOA
3006: General HOA
3006: General HOA Keys
Keys
B.2 A: Initialization Parameters
Description
<3>
<3>
<4>
A1-03 is initially set to "6008" from the factory,
although the keypad will always display "0".
This parameter is not settable. It is used as a
monitor only.
<3>
<3>
<4>
Values
Page
Default: 0
Range: 0 to 6
Default: 2
210
Range: 0 to 3
Default: 0
Range: 0, 2
Default: 0
Range: 0 to 5550;
210
6008 to 6014;
7770, 7771
Default: 0000
Min.: 0000
Max.: 9999
Default: 0
Range: 0 to 2; 5, 6;
8 to 14
Default: 0
Range: 0, 3005,
212
3006
B