Auto-Tuning - YASKAWA iQpump1000 User Manual

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

5.8

Auto-Tuning

u
Types of Auto-Tuning
The drive offers different types of Auto-Tuning for induction motors. Refer to the tables below to select the type of Auto-
Tuning that bests suits the application.
n
Auto-Tuning for Induction Motors
This feature automatically sets the V/f pattern and motor parameters E1-oo and E2-oo for an induction motor.
Type
Stationary Auto-Tuning for
Line-to-Line Resistance
Rotational Auto-Tuning for
V/f Control
Stationary
Auto-Tuning 2
Table 5.9
lists the data that must be entered for Auto-Tuning. Make sure this data is available before starting Auto-Tuning.
The necessary information is usually listed on the motor nameplate or in the motor test report provided by the motor
manufacturer.
Input Value
Control Mode
Motor rated power
Motor rated voltage
Motor rated current
Motor rated frequency
Number of motor poles
Motor rated speed
Motor no-load current
Motor rated slip
Motor iron loss
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Table 5.8 Types of Auto-Tuning for Induction Motors
Setting
Application Conditions and Benefits
• The drive is used in V/f Control and other Auto-Tuning selections are
not possible.
• Perform when entering motor data manually while using motor cables
longer than 50 m.
• Drive and motor capacities differ.
T1-01 = 2
• Tunes the drive after the cable between the drive and motor has been
replaced with a cable over 50 m long. Assumes Auto-Tuning has
already been performed.
• Should not be used for any vector control modes unless the motor cable
has changed.
• Recommended for applications using Speed Estimation Speed Search
or using the Energy Saving function in V/f Control.
T1-01 = 3
• Assumes motor can rotate while Auto-Tuning is executed. Increases
accuracy for certain functions like torque compensation, slip
compensation, Energy Saving, and Speed Search.
• Motor and load cannot be decoupled and the load is higher than 30%.
• A motor test report is available. After entering the no-load current and
T1-01 = 4
the rated slip, the drive calculates and sets all other motor-related
parameters.
Table 5.9 Auto-Tuning Input Data
Input Parameter
Unit
A1-02
T1-02
kW
T1-03
Vac
T1-04
A
T1-05
Hz
T1-06
-
T1-07
r/min
T1-09
A
T1-10
Hz
T1-11
W
Tuning Type (T1-01)
2
3
Line-to-Line
Rotational for V/f
Resistance
Control
0, 2
0
YES
YES
YES
YES
YES
YES
YES
YES
YES
5.8 Auto-Tuning
Control Mode
V/f
OLV
YES
YES
YES
YES
4
Stationary 2
2
YES
YES
YES
YES
YES
5
YES
YES
YES
297

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents