4.7 Basic iQpump Setup and Application Preset Parameters
3006: General HOA Keys
n
b1-01: Frequency Reference Selection 1
Selects the frequency reference source 1 for the REMOTE mode.
Note:
If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator LED
on the digital operator will light and the STOP indicator will flash.
No.
b1-01
In order to run the drive and motor, the drive must receive a Run command and an Auto Setpoint command. Parameter b1-01
specifies the origin of the Auto setpoint when in AUTO Mode. Switch to AUTO mode by pressing the AUTO button on the
HOA keypad while the drive is stopped.
Note:
If a Run command is input to the drive without a corresponding Auto setpoint, the Run indicator on the HOA keypad will turn on and the
STOP indicator on the keypad will blink.
If the drive should follow the "HAND Reference" set by the HOA keypad, use HAND Mode by pressing the HAND key and
set P5-01 to "1: Hand Reference (P5-02)." The HAND reference can then be entered into the U1-01 monitor parameter in the
"-DRIVE- " Menu.
The drive offers the ability to provide four types of "Auto Setpoint" reference sources. These Auto Setpoint reference sources
are determined by the setting of b1-01 and the drive set to AUTO Mode by pressing the AUTO key on the keypad.
Prior to programming, it is recommended to select the system units (P1-02) and the feedback device, Scaling (P1- 03) first.
P1-03 will automatically scale the drive setpoint.
Example: P1-02 = 1: PSI
P1-03 = 200, feedback range = 200 PSI.
214
AUTO Run = AUTO key + S1,
Speed = A2
HAND1 Run = S6,
Speed = P5-02
or Operator when P5-01 = 1,
otherwise Terminal A1
HAND2 Run = S7,
Speed = P5-05 or Operator
Run
Ext. Pump
Fault (N.O.)
Fault
Ext. Pump
Reset
Fault (N.O.)
Ext. Pump
Fault (N.O.)
HAND1
HAND2
Comms Run
P5-01 = 0
HAND1 Speed Ref
Def: 0 to 10 V (H3-01)
AUTO Speed Ref
Def: 4 to 20 mA (H3-09)
x
Figure 4.32 Default Port Configuration for General HOA Keys
Parameter Name
Frequency Reference Selection 1
Switch to Net Coms = S8;
AUTO Run = Auto key + Serial Run,
Speed = Serial Comms
S1
S2
Drive
S3
S4
S5
S6
S7
S8
SN
24V
+V
A1
A2
A3
AC
R+
R-
S+ S-
Serial Comms
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Setting Range
0 to 5
Default
0