B.16 U: Monitors
No.
(Addr.
Name
Hex)
U1-11
Output Terminal
(004A)
Status
<7>
U1-12
Drive Status
(004B)
U1-13
Terminal A1 Input
(004E)
Level
<7>
U1-14
Terminal A2 Input
(004F)
Level
<7>
U1-15
Terminal A3 Input
(0050)
Level
<7>
U1-16
Output Frequency after
(0053)
Soft Starter
U1-18
oPE Fault Parameter
(0061)
U1-19
MEMOBUS/Modbus
(0066)
Error Code
U1-24
Input Pulse Monitor
(007D)
U1-25
Software Number
(004D)
(Flash)
<7>
U1-26
Software No. (ROM)
(005B)
438
LCD Display
Displays the output terminal status.
U1 - 11=
Output Term Sts
Verifies the drive operation status.
U1 - 12=
Int Ctl Sts 1
Displays the signal level to analog input terminal A1.
Term A1 Level
Displays the signal level to analog input terminal A2.
Term A2 Level
Displays the signal level to analog input terminal A3.
Term A3 Level
Displays output frequency with ramp time and S-curves. Units
SFS Output
determined by o1-03.
Displays the parameter number that caused the oPE02 operation
OPE Error Code
error.
Displays the contents of a MEMOBUS/Modbus error.
U1 - 19=
Transmit Err
Displays the frequency to pulse train input terminal RP.
Term RP Inp Freq
FLASH ID
CPU 1 SW Number
ROM ID
CPU 2 SW Number
Description
00000000
1
Multi-Function
Digital Output
(terminal MD-ME-MF)
1
Multi-Function
Digital Output
(terminal M1-M2)
1
Multi-Function
Digital Output
(terminal M3-M4)
0
Not Used
1
Fault Relay
(terminal MA-MC closed
MA-MC open)
00000000
1
During run
1
During zero-speed
1
During REV
1
During fault reset
signal input
1
During speed agree
1
Drive ready
1
During alarm
detection
1
During fault detection
00000000
1
CRC Error
1
Data Length Error
0
Not Used
1
Parity Error
1
Overrun Error
1
Framing Error
1
Timed Out
0
Not Used
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Analog
Unit
Output Level
No signal output
available
No signal output
available
10 V: 100%
0.1%
10 V: 100%
0.1%
10 V: 100%
0.1%
10 V: Max
0.01 Hz
frequency
No signal output
available
No signal output
available
Determined by
1 Hz
H6-02
No signal output
available
No signal output
available