No.
P1-11
<1> Range is 0.0 to 999.9 with sign-bit "+" indicating Delta to Setpoint.
Range is 0.0 to 6000.0 in drive software versions PRG: 8551 and earlier.
n
P1-12: High Feedback Level Fault Delay Time
Sets the delay time after which a Low Feedback alarm or fault will occur. When the PID feedback rises above the P1-11 setting
for the time set in P1-12, the drive will respond based on the setting in P1-13.
No.
P1-12
n
P1-13: High Feedback Selection
Selects the drive response to a High Feedback condition. When the PID feedback rises above the P1-11 setting for the time
set in P1-12, the drive will respond based on the setting in P1-13.
No.
P1-13
High feedback detection is enabled when:
• P1-11 > 0
• Run Command present, including sleep & timer operation (standard PID, b5-09 = 0)
• Drive is running in AUTO Mode, including feedback drop detection (inverse PID, b5-09 = 1).
Setting 0: Fault
When feedback rises above the P1-11 for longer than the time set in P1-12, the drive will fault on the "HFB – High Feedback"
fault and coast to a stop.
The digital output programmed to "High Feedback" (H2-0o= 96) closes. The drive will also display the "High Feedback –
High FB Sensed" alarm. The digital output will remain closed until the fault is reset.
Setting 1: Alarm
When feedback rises above the P1-11 for longer than the time set in P1-12, the digital output programmed to "High Feedback"
(H2-0o= 96) closes and the drive displays the "High Feedback – High FB Sensed" alarm.
When feedback falls below the level determined by P1-11 and P1-14, or when one or more of the conditions that enable high
feedback detection are no longer true, the digital output will open and the alarm will clear.
Setting 2: Digital out only
When feedback rises above the P1-11 for longer than the time set in P1-12, the digital output programmed to "High Feedback"
(H2-0o= 96) closes.
When feedback falls below the level determined by P1-11 and P1-14, or when one or more of the conditions that enable high
feedback detection are no longer true, the digital output will open.
n
P1-40: Maximum Pump Speed
Sets the maximum pump speed determined by the smallest value among P1-40, E1-04, and d2-01. This parameter is not
effective when set to 0 or when set higher than E1-04 x d2-01.
When this parameter ≠ 0, maximum pump speed is internally lower limited to the minimum pump speed (largest setting among
P1-06, P4-12, and d2-02).
Note:
1. Parameter available in drive software versions PRG: 8552 and later.
2. Parameter not available in drive models 4A0930 and 4A1200.
No.
P1-40
n
P2-01: Sleep Level Type
Selects which data source the drive will use to determine if it should activate the sleep function. This parameter is application-
dependent and should be set in conjunction with the type of system data is available. Choose the data type that best represents
a low-activity condition for the system.
Note:
Set this parameter prior to changing other parameters related to the Sleep Function, as internal scaling is based on P2-01.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
4.7 Basic iQpump Setup and Application Preset Parameters
Parameter Name
High Feedback Level
Parameter Name
High Feedback Level Fault Delay Time
Parameter Name
High Feedback Selection
Parameter Name
Maximum Pump Speed
Setting Range
<1>
Setting Range
0 to 3600 s
Setting Range
0 to 2
Setting Range
0.0 to 440.0 Hz
Default
155.0 PSI
Default
5 s
Default
0
4
Default
0.0 Hz
233