4.6 iQpump Presets and Functions
Network State
Drive is in Auto Mode, Lag operation and is
holding the speed at the time it made the
switch from being a lead drive to a lag. Speed
is held until P9-07 time expires. The Home
screen will display U1-01 instead of U5-99.
Drive is in Auto Mode, Lag operation and is
running at the speed set in P9-06. The Home
Screen will display U1-01 instead of U5-99.
Drive is in AUTO Mode, Lag operation and
is following the speed of the current Lead
drive. The Home screen will display U1-01
instead of U5-99.
Drive is in AUTO Mode, Lead operation with
Geothermal Enabled. The Home screen will
display U1-01 instead of U5-99
n
PI Feedback via Network
The Network PI Feedback comes from a drive on the network with a valid analog PI feedback source and can be used as the
primary or secondary feedback source for a networked drive.
Set P9-02 to 0 if a drive has an analog PI feedback device installed and switching to network as a backup is not desired.
if a drive has an analog PI feedback device installed and the network PI feedback is considered as a backup, set P9-02 to 1 for
no alarm message when switched and set P9-02 to 2 for an alarm.
Set P9-02 to 3 if a drive has no analog PI feedback device installed and relies solely on the analog PI feedback of another
networked drive.
Note:
Connect an analog PI feedback device to each drive for best performance.
n
Related Parameters
No.
H5-01
Drive Node Address
P1-01
Pump Mode
P9-02
Feedback Source
182
- MODE -
U1-01= 59.41
U1-02=
U1-91=
Home
- MODE -
Lag: Fixed P9-06
U1-01= 55.00
U1-02=
U1-91=
Home
- MODE -
Lag: Follow Lead
U1-01= 51.37
U1-02=
U1-91=
Home
- MODE -
Lead: Geothermal
U1-01= 48.00
U1-02=
U1-80=
Home
Parameter Name
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Display
DRV RDY
Lag: Fixed Hold
HZ
59.41Hz
99.8PSI
DRV RDY
HZ
55.00Hz
99.9PSI
DRV RDY
HZ
51.35Hz
98.9PSI
DRV RDY
HZ
44.82Hz
83.6˚F
Default: 1F (Hex)
Min.: 0
Max.: FF
Default: 0
Range: 0, 1, 3
Default: 0
Range: 0 to 3
Setting Values