YASKAWA iQpump1000 User Manual page 4

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

Step
iQpump Model
1
Identification and Mounting
To make sure you received the correct model, it is
essential to verify the iQpump nameplate with your order
and make sure the iQpump has the correct rating so it can
be used with your motor. Please check the nameplate
information as shown in the example below.
Drive Model
Number
CIMR-PW2A0021FAA
CC
:
CIMR-PW2A0021FAA
Input Power
Rating
Output
Power
Rating
6W3050 - 2 - 100
Weight
J0073D207410100
Serial
Number
UL File
Number
Check that the available power will meet the input
power requirements.
Ensure that the output power from the iQpump is
compatible with the motor requirements.
In the case of systems with more than one iQpump, follow
the above procedure for each iQpump and motor.
Mounting the iQpump
The mounting of the iQpump is extremely important
regarding environment and accessibility. Depending on your
system, there are various models available and the mounting
dimensions (footprint) may be different. Because the
mounting procedure is fairly extensive, it is beyond the scope
of this document; Refer to the iQpump1000
Quick Start Guide (Document No. TOEPYAIP1W01)
received with the iQpump, Section 2.2 Mechanical
Installation. Match the model that you received and follow
the procedure described in the manual to ensure a safe and
functional installation. In cases where the system has more
than one iQpump, refer to the proper clearances required for
adequate ventilation. Please pay particular attention to:
The clearances to be maintained around the enclosure
for adequate ventilation.
The environmental specifications such as avoiding
excessive dampness, extreme temperatures, chemical
exposure, corrosive areas, etc. to avoid damage to the
equipment and to maintain safety.
Removing and Attaching the Terminal Cover
Improper removal of the iQpump terminal cover as well as
front cover can cause extensive damage to the iQpump. To
avoid damage to these items, please pay particular attention
to the iQpump1000 Quick Start Guide TOEPYAIP1W01
Section 3.5 Removing and Attaching the Terminal Cover.
IP20/NEMA 1, UL Type 1
Open Chassis
4
Step
2
Fig.1 & 2 below show the electrical connections for the input
power and motor terminals for various iQpump models. Select
the proper diagram for the model you are installing (see Step
1). WITH POWER OFF make the appropriate connections.
Make sure to follow good wiring practices and all
applicable codes. Ensure that the equipment is grounded
Drive Spec Number
properly as shown in fig. 1
Normal
DANGER; LETHAL VOLTAGES ARE PRESENT - Before
Duty Amps
!
applying power to the iQpump, ensure that the terminal
Software
8000
cover is fastened and all wiring connections are secure.
Version
After the power has been turned OFF, wait at least five
minutes until the charge indicator extinguishes
completely before touching any wiring, circuit boards or
components.
(R/L1)
Use L1, L2 for
1Ø Input Power
Fig. 1 Input Power and Output Motor Electrical Connections for
Models: 2_0004 - 2_0056, 4_0002 - 4_0044 and 5_0003 - 50011
Protection
(Fuse or Circuit
Breaker)
Use L1, L2 for
1Ø Input Power *
Fig. 2 Input Power and Output Motor Electrical Connections for
*
Make sure the iQpump has been properly sized for single phase input
power. For best performance, the drive input supply voltage must be
equal to or greater than the motor rated voltage.
Connect Motor and
Line Power
WARNING DO NOT CONNECT ANY OF THE
FOLLOWING TERMINALS TO EARTH GROUND
-
B1
B2
+1
+2
+3
DC Bus terminals
location varies by
model.
(T/L3)
(U/T1)
(S/L2)
Connect to
chassis ground
Input
Protection
(Fuse or Circuit
Breaker)
L1 L2 L3
Use L1, L2, L3 for
3Ø Induction
*
3Ø Input Power
motor
NOT USED
BUS TERMINALS:
DO NOT CONNECT TO GROUND
(U/T1)
(W/T3)
(R/L1)
(S/L2)
(T/L3)
(V/T2)
To change direction of motor
rotation swap any two of the
Connect to
chassis
Input
ground
L1 L2 L3
Connect
frame to
ground
Use L1, L2, L3 for
3Ø Induction
3Ø Input Power
motor
Models: 2_0110 & Larger and 4_0058 & Larger
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Step
Real-time
3
Clock Setup
This step shows how to setup the
iQpump real-time clock for first
use.
Note:
If clock is not set the drive
can still be programmed and
operated, but ALM light will flash
every 30s and showing Clock
Not Set message.
Power up the drive and set the
real-time Clock. The real-time
Clock setup screen will appear at
first power up.
Press
to set the clock.
Note:
After the real-time clock is
set the real-time clock setup
screen will not show again unless
parameter o4-17 is set to "Set".
(W/T3)
Real-time Clock Setup Screen
(V/T2)
To change
direction of
motor rotation
swap any two
of the three
motor leads.
Connect
frame to
ground
Use
to move cursor to
The left and
cursor to the right
use
three motor leads.
When date and time are set
press
to save.
Example:
Jun 12
Note:
Do NOT adjust sec per
month.
to move
to adjust.
th
2012, 7:35am