YASKAWA iQpump1000 User Manual page 282

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

5.3 Alarm Detection
HOA Keypad Display
Terminal So (H1-0o = 95) has been open
for the time set in P4-26, Remote Drive
Disable On-Delay, when P4-25, Remote
Drive Disable Selection, was set to 1
(N.C.).
HOA Keypad Display
rUn
Cause
A motor switch command was entered
during run.
HOA Keypad Display
SE
Cause
A digital input set to 67H (MEMOBUS/
Modbus test) was closed while the drive
was running.
HOA Keypad Display
SPL
Suction Pressure Loss
Cause
An analog input programmed for setting 23
"WaterLvl/Suction" has dropped below 3
mA or risen above 21 mA for longer than 1
second.
Digital Operator Display
THo
<1>
Cause
The motor thermistor is not connected
properly.
<1> Detected in models 4A0930 and 4A1200.
HOA Keypad Display
TrPC
Cause
IGBTs have reached 90% of their expected
performance life.
HOA Keypad Display
UL3
Cause
Parameter settings are not appropriate for
the load
There is a fault on the machine side
HOA Keypad Display
UL4
282
Remove conditions causing the terminal to open.
Motor Switch during Run
A command to switch motors was entered during run.
Change the operation pattern so that the motor switch command is entered while the drive is stopped.
MEMOBUS/Modbus Communication Test Mode Error
Note:
This alarm will not trigger a multi-function output terminal that is set for alarm output
(H2-oo = 10).
Stop the drive and run the test again.
Suction Pressure Loss
Wire-break detection for suction pressure.
Repair pressure sensor or wiring.
Thermistor Disconnect
The thermistor used to detect motor temperature has become disconnected.
Check the thermistor wiring.
IGBT Maintenance Time (90%)
IGBTs have reached 90% of their expected performance life.
Replace the drive.
Undertorque Detection 1
The current has fallen below the minimum value set for torque detection (L6-02) for longer than the allowable
time (L6-03).
Check the settings of parameters L6-02 and L6-03.
Check the load for any problems.
Undertorque Detection 2
The current has fallen below the minimum value set for torque detection (L6-05) for longer than the allowable
time (L6-06).
Minor Fault Name
Minor Fault Name
Possible Solution
Minor Fault Name
Possible Solution
Minor Fault Name
Possible Solution
Minor Fault Name
Possible Solutions
Minor Fault Name
Possible Solution
Minor Fault Name
Possible Solution
Minor Fault Name
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual