YASKAWA iQpump1000 User Manual page 368

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

B.7 F: Options
B.7 F: Options
u
F4: Analog Monitor Card (AO-A3)
No.
(Addr.
Name
Hex)
F4-01
Terminal V1 Monitor
(0391)
Selection
F4-02
Terminal V1 Monitor
(0392)
Gain
F4-03
Terminal V2 Monitor
(0393)
Selection
F4-04
Terminal V2 Monitor
(0394)
Gain
F4-05
Terminal V1 Monitor
(0395)
Bias
F4-06
Terminal V2 Monitor
(0396)
Bias
F4-07
Terminal V1 Signal
(0397)
Level
F4-08
Terminal V2 Signal
(0398)
Level
u
F5: Digital Output Card (DO-A3)
No.
(Addr.
Name
Hex)
F5-01
Terminal P1-PC Output
(399)
Selection
F5-02
Terminal P2-PC Output
(39A)
Selection
F5-03
Terminal P3-PC Output
(39B)
Selection
F5-04
Terminal P4-PC Output
(39C)
Selection
F5-05
Terminal P5-PC Output
(39D)
Selection
F5-06
Terminal P6-PC Output
(39E)
Selection
F5-07
Terminal M1-M2
(39F)
Output Selection
F5-08
Terminal M3-M4
(3A0)
Output Selection
F5-09
DO-A3 Output Mode
(3A1)
Selection
368
LCD Display
Sets the monitor signal for output from terminal V1. Set this
parameter to the last three digits of the desired Uo-oo
AO Ch1 Select
monitor. Some U parameters are available only in certain control
modes.
Sets the gain for voltage output via terminal V1.
AO Ch1 Gain
Sets the monitor signal for output from terminal V2. Set this
parameter to the last three digits of the desired Uo-oo
AO Ch2 Select
monitor. Some U parameters are available only in certain control
modes.
Sets the gain for voltage output via terminal V2.
AO Ch2 Gain
Sets the amount of bias added to the voltage output via terminal
V1.
AO Ch1 Bias
Sets the amount of bias added to the voltage output via terminal
V2.
AO Ch2 Bias
AO Opt Level Ch1
0: 0 to 10 V
0: 0-10 VDC
1: -10 to 10 V
1: -10 +10 VDC
AO Opt Level Ch2
0: 0 to 10 V
0: 0-10 VDC
1: -10 to 10 V
1: -10 +10 VDC
LCD Display
Sets the function for contact output terminals M1-M2, M3-M4,
DO Ch1 Select
and photocoupler output terminals P1 through P6.
Refer to H2: Multi-Function Digital Outputs on page 379
DO Ch2 Select
setting selections.
DO Ch3 Select
DO Ch4 Select
DO Ch5 Select
DO Ch6 Select
DO Ch7 Select
DO Ch8 Select
DO Function Sel
0: Output terminals are each assigned separate output functions.
0: 8ch Individual
1: Binary code output.
1: Binary Output
2: Use output terminal functions selected by parameters F5-01
2: 8ch Selected
through F5-08.
Description
Description
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Values
Page
Default: 102
Range: 000 to
999
Default: 100.0%
Min.: -999.9
Max.: 999.9
Default: 103
Range: 000 to
999
Default: 50.0%
Min.: -999.9
Max.: 999.9
Default: 0.0%
Min.: -999.9
Max.: 999.9
Default: 0.0%
Min.: -999.9
Max.: 999.9
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Values
Page
Default: 0
Range: 0 to 192
for
Default: 1
Range: 0 to 192
Default: 2
Range: 0 to 192
Default: 4
Range: 0 to 192
Default: 6
Range: 0 to 192
Default: 37
Range: 0 to 192
Default: F
Range: 0 to 192
Default: F
Range: 0 to 192
Default: 0
Range: 0 to 2