No.
(Addr.
Name
Hex)
H1-46
(09F0)
Terminal S6 Off-Delay
Time
<2>
H1-47
(09F1)
Terminal S7 Off-Delay
Time
<2>
H1-48
(09F2)
Terminal S8 Off-Delay
Time
<2>
<1> Value in parenthesis is the default setting when a 3-Wire initialization is performed (A1-03 = 3330).
<2> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
<3> Default is 0.00 s and range is 0.00 to 300.00 in drive software versions PRG: 8553 and earlier.
H1-oo
Function
Setting
0
3-Wire sequence
External Reference 1/2
2
Selection
Multi-Step Speed
3
Reference 1
Multi-Step Speed
4
Reference 2
Multi-Step Speed
5
Reference 3
6
Jog reference selection jog Freq Ref
Accel/decel time
7
selection 1
Baseblock command
8
(N.O.)
Baseblock command
9
(N.C.)
A
Accel/decel ramp hold
Drive overheat alarm
B
(oH2)
Analog terminal input
C
selection
F
Through mode
10
Up command
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
LCD Display
Sets the length of time needed for Terminal S6 to be open before
Term S6 OffDelay
the drive removes the programmed function.
Sets the length of time needed for Terminal S7 to be open before
Term S7 OffDelay
the drive removes the programmed function.
Sets the length of time needed for Terminal S8 to be open before
Term S8 OffDelay
the drive removes the programmed function.
H1 Multi-Function Digital Input Selections
LCD Display
Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence)
3-Wire Control
Terminals S1 and S2 are automatically set up for the Run command and Stop
command.
Open: Run command and frequency reference source 1 (determined by b1-01 and
b1-02)
External Ref 1/2 Sel
Closed: Run command and frequency reference source 2 (determined by b1-15
and b1-16)
When input terminals are set to Multi-Step Speed References 1 through 3,
Multi-Step Ref 1
switching combinations of those terminals will create a multi-step speed sequence
using the frequency references set in d1-01 through d1-08.
When input terminals are set to Multi-Step Speed References 1 through 3,
Multi-Step Ref 2
switching combinations of those terminals will create a multi-step speed sequence
using the frequency references set in d1-01 through d1-08.
When input terminals are set to Multi-Step Speed References 1 through 3,
Multi-Step Ref 3
switching combinations of those terminals will create a multi-step speed sequence
using the frequency references set in d1-01 through d1-08.
Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other
reference sources.
Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel
Multi-Acc/Dec 1
time 2
(set in C1-03, C1-04).
Ext BaseBlk N.O.
Closed: No drive output
Ext BaseBlk N.C.
Open: No drive output
Open: Accel/decel is not held
Acc/Dec RampHold
Closed: The drive pauses during acceleration or deceleration and maintains the
output frequency.
OH2 Alarm Signal
Closed: Closes when an oH2 alarm occurs
Open: Function assigned by H3-14 is disabled.
Term A2 Enable
Closed: Function assigned by H3-14 is enabled.
Select this setting when using the terminal in a pass-through mode. The terminal
Term Not Used
does not trigger a drive function but can be used as digital input for the controller
the drive is connected to.
The drive accelerates when the Up command terminal closes, and decelerates when
the Down command closes. When both terminals are closed or both are open, the
Up Command 1
drive holds the frequency reference. The Up and Down commands must always
be used in conjunction with one another.
B.8 H Parameters: Multi-Function Terminals
Description
Description
Values
Page
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
<3>
Page
B
375