YASKAWA iQpump1000 User Manual page 412

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

B.12 P: Pump Parameters
<2> Available in drive software versions PRG: 8553 and later. Not available in drive models 4A0930 and 4A1200.
<3> Unit text is set by P1-18, Prime Loss Detection Method.
<4> Available in drive software versions PRG: 8551 and later.
<5> Maximum value is 300.0 in drive software versions PRG: 8553 and earlier.
<6> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
u
P5: Pump HAND Mode
No.
(Addr.
Name
Hex)
P5-01
(0D2C) HAND Mode Ref
Source
P5-02
(0D2D) HAND Reference 1
P5-03
HAND/AUTO During
(0D2E)
Run Selection
P5-04
HAND Key Function
(0D2F)
Selection
P5-05
(0D30) HAND Reference 2
P5-06
(0D31) HAND Ref. 1 Loss of
Prime Level
P5-07
(0D32) HAND Ref. 2 Loss of
Prime Level
HAND References Set
P5-09
via Motor Operated Pot
(0D34)
Selection
<1> Unit text is set by P1-18, Prime Loss Detection Method.
412
LCD Display
Sets the HAND Mode reference.
0: Analog input
Hand Mode 1 Src
0: Analog Input
Note:
1: Hand Ref 1 (OPR)
1: P5-02 (HAND reference)
Sets the frequency reference used when HAND Mode is active
and P5-01 is set to 1.
HAND Reference 1
Selects whether the drive will permit switching between HAND
HAND/AUTO @Run
and AUTO Modes while running.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Oper HAND Key
Enables and disables the HAND key on the HOA keypad.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Sets the frequency reference used when HAND Mode 2 is
active.
HAND Reference 2
Detects loss of prime in the pump.
When the measured quantity determined by P1-18 drops below
this level for the time set in P1-20 and the output frequency is
HandRef1 LOP Lvl
at the level set in P5-02, a "Loss of Prime" condition occurs.
The drive responds to the "Loss of Prime" condition depending
on the setting of P1-22, Loss of Prime Selection.
Detects loss of prime in the pump.
When the measured quantity determined by P1-18 drops below
this level for the time set in P1-20 and the output frequency is
HandRef2 LOP Lvl
at the level set in P5-05, a "Loss of Prime" condition occurs.
The drive responds to the "Loss of Prime" condition depending
on the setting of P1-22, Loss of Prime Selection.
Selects whether parameters P5-02 and P5-05 are changed via
Hand MOP Sel
MOP from the home screen.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Description
Analog input is defaulted to input A3 (0-10 V).
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Values
Page
Default: 1
Range: 0, 1
Default: 40.0 Hz
Min.: 0
240
Max.: [E1-04]
Default: 0
Range: 0, 1
Default: 1
240
Range: 0, 1
Default: 0.0 Hz
Min.: 0.0
Max.: [E1-04]
Default: 0.0 A
<1>
Min.: 0.0
Max.: 1000.0
Default: 0.0 A
<1>
Min.: 0.0
Max.: 1000.0
Default: 0
Range: 0, 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents