B.12 P: Pump Parameters
No.
(Addr.
Name
Hex)
P4-11
(0D04) Thrust Bearing
Acceleration Time
P4-12
(0D05) Thrust Bearing
Frequency
P4-13
(0D06) Thrust Bearing
Deceleration Time
P4-14
Two Motor Alternation
(0D07)
Selection
<6>
P4-15
Two Motor Alternation
(0D08)
Operation Selection
<6>
P4-16
Two Motor Alternation
(0D09)
Time
<6>
P4-17
(0D0A) Utility Start Delay
P4-18
(0D0B)
Differential Level
<6>
P4-19
(0D0C)
Differential Level
Detection Time
<6>
P4-20
Differential Level
(0D0D)
Detection Selection
<6>
P4-21
Low City Input Select
(0D0E)
P4-22
(0D0F) Low City On-Delay
Time
P4-23
(0D10) Low City Off-Delay
Time
410
LCD Display
Sets the time at which the drive output frequency will ramp up
to the reference frequency set in P4-12.
Thrust Acc. Time
The drive will accelerate to this frequency in the time set to
P4-11. The drive will decelerate from the frequency in the time
set to P4-13.
Thrust Freq.
WARNING! Sudden Movement Hazard. If the drive is
powered down while running, it will automatically initiate
an internal Run command upon power-up.
Sets the amount of time it takes to bring the drive from the Thrust
Frequency set in P4-12 to stop when Thrust Mode is active.
When the Run command is removed while the drive is operating
Thrust Dec Time
in Thrust Mode above the Thrust Frequency, the time set in this
parameter is used when the frequency reference is at or below
the thrust frequency.
2Motor Alternate
Enables and disables the alternation feature
0: Disabled
0: Disable
1: Enabled
1: Enable
2: Motor 1 Only
2: Motor 1 Only
3: Motor 2 Only
3: Motor 2 Only
Determines drive behavior when the internal alternation timer
2Motor Alt Oper
expires.
0: Wait For Stop
0: Wait For Stop
1: Immediate
1: Immediate (Auto mode only)
Sets the amount of time each motor will run before the drive
2Motor Alt Time
switches to the other motor.
Sets the amount of time that the drive will delay starting if a Run
command is present at power-up.
When P1-01, Pump Mode, is set to 3 (MEMOBUS network),
Utility Delay
the drive is unavailable to the network (Pump Off Network)
when the function is active.
Setting this parameter to 0.0 disables the function.
Sets the maximum difference allowed between the PID
Feedback and the Differential Feedback.
Differential Lvl
The drive will respond based on the setting in P4-20 when the
difference exceeds the value set in this parameter for the time
set in P4-19.
Sets the amount of time that the difference between PID
Diff Lvl DetTime
Feedback and the Differential Feedback must exceed the P4-18
value before responding based on the P4-20 value.
Determines drive response during a "Differential Detected"
Diff Lvl Det Sel
condition.
0: Fault
0: Fault (and Digital Out)
1: Alarm
1: Alarm (and Digital Out)
2: Digital Output
2: Digital Out Only
Selects the type of pressure switch connected to the "Low City
Press" digital input (H1-0o = 73).
Low City In Sel
0: Normally open (closed indicates the Low City Pressure
0: Normally Open
condition)
1: Normally Closed
1: Normally closed (open indicates the Low City Pressure
condition)
Sets the amount of time a Low City Pressure condition needs to
be present before the drive will stop.
Low City On Dly
Sets the amount of time a Low City Pressure condition needs to
be absent before the drive will restart.
Low City Off Dly
Description
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Values
Page
Default: 1.0 s
Min.: 0.0
Max.: 600.0
Default: 30.0 Hz
Min.: 0.0
239
Max.: [E1-04]
Default: 5.0 s
Min.: 0.0
Max.: 600.0
Default: 0
Range: 0 to 3
Default: 0
Range: 0, 1
Default: 24.0 H
Min.: 0.1
Max.: 100.0
Default: 0.2 min
Min.: 0.0
239
Max.: 1000.0
Default: 10.0
<1>
PSI
Min.: 0.0
Max.: 6000.0
Default: 10 sec
Min.: 0
Max.: 3600
Default: 0
Range: 0 to 2
Default: 1
Range: 0, 1
Default: 10 s
Min.: 1
Max.: 1000
Default: 5 s
Min.: 0
Max.: 1000