No.
(Addr.
Name
Hex)
U4-21
Run Command Source
(07DD)
Selection
MEMOBUS/Modbus
U4-22
Communications
(07DE)
Reference
U4-23
Communication Option
(07DF)
Card Reference
U4-32
Motor Temperature
(07FB)
(NTC)
U4-37
oH Alarm Location
(1044)
Monitor
U4-38
FAn Alarm Location
(1045)
Monitor
U4-39
voF Alarm Location
(1046)
Monitor
<1> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 0099H.
<2> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 009BH.
<3> Display is in the following units:
2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.
<4> The values of U1-03, U2-05, and U4-13 are displayed on the digital operator in units of amperes. When those monitors are checked using
MEMOBUS/Modbus communications, the monitor values in MEMOBUS/Modbus communications are displayed as: numeric value / 8192 × drive
rated current (A) from the condition "192 (maximum value) = drive rated current (A)"
<5> When reading the value of this monitor via MEMOBUS/Modbus a value of 8192 is equal to 100% of the drive rated output current.
<6> Monitor is available through the Quick Monitor screen.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
LCD Display
Displays the source for the Run command as XY-nn.
X: Indicates which Run source is used:
1 = Reference 1 (b1-02)
Y: Input power supply data
0 = Digital operator
1 = External terminals
3 = MEMOBUS/Modbus communications
4 = Communication option card
nn: Run command limit status data
00: No limit status.
01: Run command was left on when stopped in the PRG mode
Run Cmd Source
02: Run command was left on when switching from LOCAL to
REMOTE operation
03: Waiting for soft charge bypass contactor after power up (Uv
or Uv1 flashes after 10 s)
04: Waiting for "Run command prohibited" time period to end
05: Fast Stop (digital input, digital operator)
06: b1-17 (Run command given at power-up)
07: During baseblock while coast to stop with timer
08: Frequency reference is below minimal reference during
baseblock
09: Waiting for Enter command
Displays the drive control data set by MEMOBUS/Modbus
MEMOBUS Ref Reg
communications register no. 0001H as a four-digit hexadecimal
number.
Displays drive control data set by an option card as a four-digit
Option Ref Reg
hexadecimal number.
Displays the motor temperature (NTC).
U4-32 will display "20 °C" when a multi-function analog input
is not set for motor thermistor input (H1-oo = 17H). Monitor
Motor Temperature
is only present when a digital input is programmed for 17
(NTC)
(Thermistor Input).
Note:
Displays the module where the oH alarm occurred as a binary
number.
OH Alarm Axis
Note:
Displays the module where the FAn alarm occurred as a binary
number.
FAN Alarm Axis
Note:
Displays the module where the voF alarm occurred as a binary
number.
VOF Alarm Axis
Note:
Description
This monitor is only displayed in models 4A0930
and 4A1200.
This monitor is only displayed in models 4A0930
and 4A1200.
This monitor is only displayed in models 4A0930
and 4A1200.
This monitor is only displayed in models 4A0930
and 4A1200.
B.16 U: Monitors
Analog
Unit
Output Level
No signal output
available
No signal output
available
No signal output
available
200 °C
1 °C
No signal output
available
No signal output
available
No signal output
available
B
445