B.13 Q: PID Controller Parameters
B.13 Q: PID Controller Parameters
u
Q1: Preset Setpoint
No.
(Addr.
Name
Hex)
Q1-01
PID Controller Setpoint
(0E58)
1
Q1-02
PID Controller Setpoint
(0E59)
2
Q1-03
(0E5A) PID Controller Setpoint
3
Q1-04
(0E5B) PID Controller Setpoint
4
Q1-09
PID Setpoint Set via
(0E60)
Motor Operated Pot
<1> Unit text is set by P1-02, System Units. Scaling is set by P1-03, Feedback Device Scaling.
u
Q2: Geothermal Mode Setup
No.
(Addr.
Name
Hex)
Q2-01
Minimum Geothermal
(0E8A)
Temperature Input
Q2-02
Maximum Geothermal
(0E8B)
Temperature Input
Q2-03
(0E8C) Minimum Geothermal
Speed
Q2-04
(0E8D) Maximum Geothermal
Speed
Q2-05
Low Temperature to
(0E8E)
Run at Maximum
Geothermal Speed
Q2-06
Low Temperature to
(0E8F)
Run at Minimum
Geothermal Speed
Q2-07
High Temperature to
(0E90)
Run at Minimum
Geothermal Speed
Q2-08
High Temperature to
(0E91)
Run at Maximum
Geothermal Speed
422
LCD Display
Sets the PID Setpoint when b1-01 is set to 0.
Setpoint 1
Sets the PID Setpoint when the "Multi Setpoint 1" or "Alternate
Multi Setpoint 1" multi-function digital input is closed.
Setpoint 2
Sets the PID Setpoint when the "Multi Setpoint 2" or "Alternate
Multi Setpoint 2" digital input is closed.
Setpoint 3
Sets the PID Setpoint when the "Multi Setpoint 1" and "Multi
Setpoint 2" or "Alternate Multi Setpoint 3" multi-function
Setpoint 4
digital inputs are closed.
Selects whether parameters Q1-01 to Q1-04 are changed via
Setpoint MOP
MOP from the home screen.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
LCD Display
Sets the temperature that corresponds to a 0 V (or 4 mA) analog
MinGeothrm Scale
input.
Sets the temperature that corresponds to a 10 V (or 20 mA)
MaxGeothrm Scale
analog input.
Sets the frequency reference characteristics based on the set
temperature points and the corresponding frequency.
MinGeothrm Speed
For proper operation, set the parameters as follows:
Q2-04 > Q2-03 and Q2-08, Q2-08 > Q2-07 > Q2-06 > Q2-05
MaxGeothrm Speed
Low Temp @ Max
Low Temp @ Min
High Temp @ Min
High Temp @ Max
Description
Description
Frequency
Reference (Hz)
Q2-04
Q2-03
Q2-05
Q2-06
Q2-07
Temperature °F
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Values
Default: 0.0
Min.: 0.0
Max.: 6000.0
<1>
Default: 0.0
Min.: 0.0
Max.: 6000.0
<1>
Default: 0.0
Min.: 0.0
Max.: 6000.0
<1>
Default: 0.0
Min.: 0.0
Max.: 6000.0
<1>
Default: 0
Range: 0, 1
Values
Default: 0.0 °F
Min.: -110.0
Max.: 320.0
Default: 120.0 °F
Min.: -110.0
Max.: 320.0
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
Default: 60.0 Hz
Min.: 0.0
Max.: 400.0
Default: 55.0 °F
Min.: -110.0
Max.: 320.0
Default: 65.0 °F
Min.: -110.0
Q2-08
Max.: 320.0
Default: 75.0 °F
Min.: -110.0
Max.: 320.0
Default: 85.0 °F
Min.: -110.0
Max.: 320.0
Page
241
Page