Setting 2: 4 to 20 mA
Setting 3: 0 to 20 mA
n
H3-06: Terminal A3 Function Selection
Determines the function assigned to analog input terminal A3.
No.
H3-06
n
H3-07, H3-08: Terminal A3 Gain and Bias Setting
Parameter H3-07 sets the level of the selected input value that is equal to 10 Vdc input at terminal A3 (gain).
Parameter H3-08 sets the level of the selected input value that is equal to 0 V input at terminal A3 (bias).
No.
H3-07
H3-08
n
H3-09: Terminal A2 Signal Level Selection
Selects the input signal level for analog input A2. Set Jumper S1 on the terminal board accordingly for a voltage input or
current input.
No.
H3-09
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc.
Setting 1: 0 to 10 Vdc Bipolar
The input level is -10 to 10 Vdc.
Setting 2: 4 to 20 mA
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
Setting 3: 0 to 20 mA
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
n
H3-10: Terminal A2 Function Selection
Determines the function assigned to analog input terminal A2.
No.
H3-10
n
H3-11, H3-12: Terminal A2 Gain and Bias Setting
Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Use both parameters to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same way
as parameters H3-03 and H3-04 for analog input A1.
No.
H3-11
H3-12
n
H4-01, H4-04: Multi-Function Analog Output Terminal FM, AM Monitor Selection
Sets the desired drive monitor parameter Uo-oo to output as an analog value via terminal FM and AM.
Operation Status Monitors on page 437
monitor can be used for analog output.
Example: Enter "103" for U1-03.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
4.7 Basic iQpump Setup and Application Preset Parameters
Name
Terminal A3 Function Selection
Name
Terminal A3 Gain Setting
Terminal A3 Bias Setting
Name
Terminal A2 Signal Level Selection
Refer to Setting 0: 0 to 10 Vdc on page
Refer to Setting 1: 0 to 10 Vdc Bipolar on page
Name
Terminal A2 Function Selection
Name
Terminal A2 Gain Setting
Terminal A2 Bias Setting
for a list of all monitors. The "Analog Output Level" column indicates whether a
Setting Range
0 to 31
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Setting Range
0 to 3
225.
225.
Setting Range
0 to 32
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
Default
20
Default
100.0%
0.0%
Default
2
Default
B
4
Default
100.0%
0.0%
Refer to U1:
227