YASKAWA iQpump1000 User Manual page 223

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

Setting
7
Accel/decel time selection 1
8
Baseblock command (N.O.)
9
Baseblock command (N.C.)
A
Accel/decel ramp hold
B
Drive overheat alarm (oH2)
C
Analog terminal input selection
F
Through mode
10
Up command
11
Down command
12
Forward Jog
13
Reverse Jog
14
Fault reset
15
Fast Stop (N.O.)
17
Fast Stop (N.C.)
18
Timer function input
19
PID disable
1A
Accel/decel time selection 2
1B
Program lockout
1E
Reference sample hold
20 to 2F Ext. pump fault
30
PID integral reset
31
PID integral hold
Multi-Step Speed
32
Reference 4
34
PID soft starter cancel
35
PID input level selection
Forward run command
40
(2-Wire sequence)
Reverse run command
41
(2-Wire sequence)
Run command
42
(2-Wire sequence 2)
FWD/REV command
43
(2-Wire sequence 2)
47
Node setup
51
Sequence Timer Disable
52
Sequence Timer Cancel
60
DC Injection Braking command
External Speed Search
61
command 1
<1> Available in drive software versions PRG: 8552 and later.
Not available in drive models 4A0930 and 4A1200.
n
H2-01 to H2-03: Terminal M1-M2, M3-M4, and MD-ME-MF Function Selection
The drive has three multi-function output terminals.
H2-02, and H2-03.
No.
H2-01
Terminal M1-M2 Function Selection (relay)
H2-02
Terminal M3-M4 Function Selection (relay)
H2-03
Terminal MD-ME-MF Function Selection (relay)
<1> Default is F: Through Mode in drive software versions PRG: 8551 and earlier.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Function
Table 4.22
Parameter Name
4.7 Basic iQpump Setup and Application Preset Parameters
Page
Setting
External Speed Search
62
command 2
63
Field weakening
65
KEB Ride-Thru 1 (N.C.)
66
KEB Ride-Thru 1 (N.O.)
67
Communications test mode
68
High Slip Braking (HSB)
6A
Drive enable
73
Low City Press
75
Up 2 command
76
Down 2 command
7A
KEB Ride-Thru 2 (N.C.)
7B
KEB Ride-Thru 2 (N.O.)
80
HAND Mode
81
HAND Mode 2
<1>
PI Switch to Aux
82
83
Alternate Multi-Setpoint (Q1-02)
84
Alternate Multi-Setpoint (Q1-03)
85
Alternate Multi-Setpoint (Q1-04)
88
Volute-Thermostat Normally Open
89
Volute-Thermostat Normally Closed
8C
Disable Pre-Charge
8D
Multi Setpoint 1
8E
Multi Setpoint 2
8F
Low Water Level
90
High Water Level
92
Reset Accum
95
Remove Drive Disable
A8
Secondary PI Disable (N.O.)
A9
Secondary PI Disable (N.C.)
AA
Secondary PI Inverse Operation
AB
Secondary PI Integral Reset
AC
Secondary PI Integral Hold
AD
Select Secondary PI Parameters
AF
Emergency Override Forward Run
B0
Emergency Override Reverse Run
lists the functions available for these terminals using H2-01,
Function
Setting Range
0 to 192
37: During Frequency Output
0 to 192
42: Pressure Reached
0 to 192
Page
4
Default
<1>
E: Fault
223

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents