B.16 U: Monitors
u
U5: PID Monitors
No.
(Addr.
Name
Hex)
U5-01
PID Feedback 1
(0057)
U5-02
PID Input
(0063)
U5-03
PID Output
(0064)
U5-04
PID Setpoint
(0065)
U5-05
PID Differential
(07D2)
Feedback
U5-06
PID Adjusted Feedback PID Diff Fdbk
(07D3)
U5-14
PI Output 2 Upper 4
(086B)
Digits
U5-15
PI Output 2 Lower 4
(086C)
Digits
U5-17
PI2 Setpoint
(086E)
U5-18
PI2 Feedback
(086F)
U5-19
PI2 Input
(0870)
U5-20
PI2 Output
(0871)
U5-30
Time Hr Min HHMM
(3000)
U5-31
Date Year
(3001)
U5-32
Date Mo Day MMDD
(3002)
U5-33
Date Week 000W
(3003)
U5-99
AUTO Setpoint
(1599)
<1> Unit, range and resolution is determined by b5-20, b5-38, b5-39, and b5-46
<2> Unit is determined by b5-41
<3> Unit is determined by S3-04.
446
LCD Display
Displays the PID feedback value.
PID Feedback 1
Displays the amount of PID input (deviation between PID
PID Input
setpoint and feedback).
Displays PID control output.
PID Output
Displays the PID setpoint.
PID Setpoint
Displays the 2nd PID feedback value if differential feedback is
PID Feedback 2
used (H3-oo = 16).
Displays the difference of both feedback values if differential
feedback is used (U5-01 - U5-05). If differential feedback is not
used, then U5-01 and U5-06 will be the same.
Displays the custom PI output.
PI Output2 U4
U5-14 shows the upper 4 digits while U5-15 shows the lower 4
digits. Monitors are scaled by b5-43 and b5-44.
Displays the custom PI output.
PI Output2 L4
U5-14 shows the upper 4 digits while U5-15 shows the lower 4
digits. Monitors are scaled by b5-43 and b5-44.
PI2 Setpoint
Displays the secondary PI setpoint.
PI2 Feedback
Displays the secondary PI feedback value.
Displays the secondary PI input (deviation between PI target
PI2 Input
and feedback).
PI2 Output
Displays the secondary PI control output.
Time Hr Min HHMM Displays the current time (Hours and Minutes).
Date Year
Displays the current year.
Date Mo Day MMDD Displays the current date (Month and Day).
Date Week
Displays the current date of the week.
0: Sunday
0: Sunday
1: Monday
1: Monday
2: Tuesday
2: Tuesday
3: Wednesday
3: Wednesday
4: Thursday
4: Thursday
5: Friday
5: Friday
6: Saturday
6: Saturday
Displays the PID Setpoint commanded by the source when the
Auto Setpoint
drive is in AUTO Mode.
Description
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Analog
Unit
Output Level
0.1 PSI
10 V: 100%
<1>
10 V: 100%
0.01%
10 V: 100%
0.01%
0.1 PSI
10 V: 100%
<1>
10 V: 100%
0.01%
10 V: 100%
0.01%
1
No signal output
<2>
available
0.01
No signal output
<2>
available
Dependent upon
<3>
S3-02
Dependent upon
<3>
S3-02
Dependent upon
<3>
S3-02
Dependent upon
<3>
S3-02
No signal output
1
available
No signal output
1
available
No signal output
1
available
No signal output
1
available
0.1 PSI
No signal output
available
<1>