YASKAWA iQpump1000 User Manual page 389

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
Operation at Thermistor
L1-19
Disconnect (THo)
(0444)
(NTC)
L1-20
Operation at Motor
(0445)
Overheat (oH5)
<1> Default is 1 in drive software versions PRG: 8551 and earlier.
u
L2: Momentary Power Loss Ride-Thru
No.
(Addr.
Name
Hex)
L2-01
Momentary Power Loss
(0485)
Operation Selection
L2-02
Momentary Power Loss
(0486)
Ride-Thru Time
Momentary Power Loss
L2-03
Minimum Baseblock
(0487)
Time
Momentary Power Loss
L2-04
Voltage Recovery
(0488)
Ramp Time
L2-05
Undervoltage Detection
(0489)
Level (Uv1)
L2-06
KEB Deceleration Time
(048A)
L2-07
KEB Acceleration Time
(048B)
L2-08
Frequency Gain at KEB
(048C)
Start
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
LCD Display
Determines drive response when a thermistor disconnect fault
(THo) occurs.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time set
Tho Stop sel
to C1-09)
3: Alarm only ("THo" will flash)
Note:
Determines drive response when a motor overheat fault (oH5)
occurs.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time set
OH5 Stop sel
to C1-09)
3: Alarm only ("oH5" will flash)
Note:
LCD Display
PwrL Selection
0: Disabled. Drive trips on Uv1 fault when power is lost.
0: Disabled
1: Recover within the time set in L2-02. Uv1 will be detected if
1: Enbl with Timer
power loss is longer than L2-02.
2: Enbl whl CPU act
2: Recover as long as CPU has power. Uv1 is not detected.
3: KEB Mode
3: KEB deceleration for the time set to L2-02.
4: KEB Stop Mode
4: KEB deceleration as long as CPU has power.
5: KEB Decel to Stop
5: KEB deceleration to stop.
Sets the Power Loss Ride-Thru time. Enabled only when
L2-01 = 1 or 3.
PwrL Ridethru t
Sets the minimum wait time for residual motor voltage decay
before the drive output reenergizes after performing Power Loss
Ride-Thru.
PwrL Baseblock t
Increasing the time set to L2-03 may help if overcurrent or
overvoltage occur during Speed Search or during DC Injection
Braking.
Sets the time for the output voltage to return to the preset V/f
pattern during Speed Search.
PwrL V/F Ramp t
Sets the DC bus undervoltage trip level.
PUV Det Level
Sets the time required to decelerate from the speed when KEB
was activated to zero speed.
KEB Decel Time
Sets the time to accelerate to the frequency reference when
momentary power loss is over. If set to 0.0, the active
KEB Accel Time
acceleration time is used.
Sets the percentage of output frequency reduction at the
beginning of deceleration when the KEB Ride-Thru function is
KEB Freq Red
started.
Reduction = (slip frequency before KEB) × L2-08 × 2
Description
This parameter is only available in models
4A0930 and 4A1200.
This parameter is only available in models
4A0930 and 4A1200.
Description
B.9 L: Protection Function
Values
Page
Default: 3
Range: 0 to 3
Default: 1
Range: 0 to 3
Values
Page
Default: 2
Range: 0 to 5
<1>
Default:
Min.: 0.0 s
Max.: 25.5 s
<1>
Default:
Min.: 0.1 s
Max.: 5.0 s
<1>
Default:
Min.: 0.0 s
Max.: 5.0 s
Default: 190
<2> <3>
Vdc
Min.: 150 Vdc
Max.: 210 Vdc
<3>
Default: 0.00 s
Min.: 0.00
Max.: 6000.0
<4>
Default: 0.00 s
Min.: 0.00
Max.: 6000.0
<4>
Default: 100%
Min.: 0
Max.: 300
B
389