YASKAWA iQpump1000 User Manual page 376

Ac drive intelligent pump controller
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

B.8 H Parameters: Multi-Function Terminals
H1-oo
Function
Setting
11
Down command
12
Forward Jog
13
Reverse Jog
14
Fault reset
15
Fast Stop (N.O.)
17
Fast Stop (N.C.)
18
Timer function input
19
PID disable
Accel/decel time
1A
selection 2
1B
Program lockout
1E
Reference sample hold Ref Sample Hold
20 to 2F External pump fault
30
PID integral reset
31
PID integral hold
Multi-Step Speed
32
Reference 4
34
PID soft starter cancel
35
PID input level selection PID Input Invert
376
H1 Multi-Function Digital Input Selections
LCD Display
The drive accelerates when the Up command terminal closes, and decelerates when
the Down command closes. When both terminals are closed or both are open, the
Down Command 1
drive holds the frequency reference. The Up and Down commands must always
be used in conjunction with one another.
Forward Jog
Closed: Runs forward at the Jog frequency d1-17.
Reverse Jog
Closed: Runs reverse at the Jog frequency d1-17.
Fault Reset
Closed: Resets faults if the cause is cleared and the Run command is removed.
Fast-Stop N.O.
Closed: Decelerates at the Fast Stop time set to C1-09.
Fast-Stop N.C.
Open: Decelerates to stop at the Fast Stop time set to C1-09.
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction
Timer function
with the timer function output (H2-oo = 12).
Open: PID control enabled
PID Disable
Closed: PID control disabled
Used in conjunction with an input terminal set for "Accel/decel time selection 1"
Multi-Acc/Dec 2
(H1-oo = 7), and allows the drive to switch between accel/decel times 3 and 4.
Open: Parameters cannot be edited (except for U1-01 if the reference source is
Program Lockout
assigned to the digital operator).
Closed: Parameters can be edited and saved.
Closed: Samples the analog frequency reference and operates the drive at that
speed.
Ext Pump Fault
20: NO/Always Det,
Ramp to Stop
21: NC/Always Det,
Ramp to Stop
22: NO/During RUN,
Ramp to Stop
23: N.C., During
RUN, Ramp to Stop
20: N.O., Always detected, ramp to stop
24: NO/ Always Det,
21: N.C., Always detected, ramp to stop
Coast to Stop
22: N.O., During run, ramp to stop
25: NC/Always Det,
23: N.C., During run, ramp to stop
Coast to Stop
24: N.O., Always detected, coast to stop
26: NO/During RUN,
25: N.C., Always detected, coast to stop
Coast to Stop
26: N.O., During run, coast to stop
27: NC/During RUN,
27: N.C., During run, coast to stop
Coast to Stop
28: N.O., Always detected, Fast Stop
28: NO/Always Det,
29: N.C., Always detected, Fast Stop
Fast-Stop
2A: N.O., During run, Fast Stop
29: NC/Always Det,
2B: N.C., During run, Fast Stop
Fast-Stop
2C: N.O., Always detected, alarm only (continue running)
2A: NO/During RUN,
2D: N.C., Always detected, alarm only (continue running)
Fast-Stop
2E: N.O., During run, alarm only (continue running)
2B: NC/During RUN,
2F: N.C., During run, alarm only (continue running)
Fast- Stop
2C: NO/Always Det,
Alarm Only
2D: NC/Always Det,
Alarm Only
2E: NO/ During RUN,
Alarm Only
2F: NC/During RUN,
Alarm Only
PID Intgrl Reset
Closed: Resets the PID control integral value.
Open: Performs integral operation.
PID Intgrl Hold
Closed: Maintains the current PID control integral value.
Used in combination with input terminals set to Multi-Step Speed Reference 1, 2,
Multi-Step Ref 4
and 3. Use parameters d1-09 to d1-16 to set reference values.
Open: PID soft starter is enabled.
PID SFS Cancel
Closed: Disables the PID soft starter b5-17.
Closed: Inverts the PID input signal.
Description
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual