B.8 H Parameters: Multi-Function Terminals
H1-oo
Function
Setting
<1>
PI Switch to Aux
82
Alternate Multi Setpoint
83
(Q1-02)
Alternate Multi Setpoint
84
(Q1-03)
Alternate Multi Setpoint
85
(Q1-04)
Volute-Thermostat
88
Normally Open
Volute-Thermostat
89
Normally Closed
8C
Disable Pre-Charge
8D
Multi Setpoint 1
8E
Multi Setpoint 2
8F
Low Water Level
90
High Water Level
Reset Accumulated
92
Volume
95
Remove Drive Disable Remote Drv Disbl
Secondary PI Disable
A8
(N.O.)
Secondary PI Disable
A9
(N.C.)
Secondary PI Inverse
AA
Operation
Secondary PI Integral
AB
Reset
Secondary PI Integral
AC
Hold
378
H1 Multi-Function Digital Input Selections
LCD Display
Closed: PI Auxiliary Control (Q6-oo) becomes the primary PI loop, disabling
PI Switch to Aux
the System PI controller (b5-oo). Overrides Q6-20 whenset to 0 (Disable Effect
on Speed Control).
AltMultiSP Q1-02
Closed: Q1-02 becomes the PID setpoint
AltMultiSP Q1-03
Closed: Q1-03 becomes the PID setpoint
AltMultiSP Q1-04
Closed: Q1-04 becomes the PID setpoint
Function active when the drive is running.
Closed: Drive will trip on "VLTS - Volute-TStat Flt"
Open: Thermostat fault not active
Volute-TStat NO
Note:
Function active when the drive is running.
Closed: Thermostat fault not active
Open: Drive will trip on "VLTS - Volute-TStat Flt"
Volute-TStat NC
Note:
Disable Pre-Chrg
Closed: Pre-Charge disabled.
Open: Frequency reference, Q1-01, or Q1-03 is PID Setpoint.
Multi Setpoint 1
Closed: Q1-02 or Q1-04 is PID Setpoint.
Open: Frequency reference, Q1-01, or Q1-02 is PID Setpoint.
Multi Setpoint 2
Closed: Q1-03 or Q1-04 is PID Setpoint.
Function active in AUTO Mode during normal operation, also used with Pre-
Charge function. Function logic depends on P1-30, Low Water Digital Input
Configuration.
P1-30 = 0 (Normally open)
Closed: Low water level fault
Low Water
Open: Reservoir/Tank is filled to normal level
P1-30 = 1 (Normally closed)
Closed: Reservoir/Tank is filled to normal level
Open: Low water level fault
Pre-Charge function: Function uses the low water level input as "Tank/Reservoir"
feedback to indicate that the water level has been reached.
Function active when the drive is running. Function logic depends on P1-31, High
Water Digital Input Configuration.
P1-31 = 0 (Normally open)
Closed: High water level fault
High Water
Open: Reservoir/Tank is filled to normal level
P1-31 = 1 (Normally closed)
Closed: Reservoir/Tank is filled to normal level
Open: High water level fault
Closed: Accumulated volume is reset to 0 and held at 0 if digital input remains
Reset Accum
closed.
Closed: Prevents the drive from running when active for the time set in P4-26.
Must be inactive for the time set in P4-27 to allow the drive to run again.
Note:
Closed: Disables the secondary PI controller. Output behavior depends on the
PI2 Disable N.O.
setting of S3-12.
Closed: Enables the secondary PI controller. Output behavior depends on the
PI2 Disable N.C.
setting of S3-12 when open.
Closed: Changes the sign of the secondary PI controller input (reverse acting PI
PI2 Invert
control).
Closed: Resets the secondary PI controller integral value.
PI2 Intgrl Reset
Closed: Locks the value of the secondary PI controller integral value.
PI2 Intgrl Hold
Description
Setting H1-oo = 88 and 89 simultaneously will trigger a "VLTS -
Volute-TStat Flt".
Setting H1-oo = 88 and 89 simultaneously will trigger a "VLTS -
Volute-TStat Flt".
Parameter P4-25 determines if this input is normally open or
normally closed.
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
Page