B.17 Defaults by Drive Model
No.
−
o2-04
E2-11
b3-06
Speed Search current 1
Current Control Gain during Speed Search (Speed
b3-08
Estimation Type)
C6-02
Carrier frequency
E2-01
Motor rated current
E2-02
Motor rated slip
E2-03
Motor no-load current
E2-05
Motor line-to-line resistance
E2-06
Motor leakage inductance
E2-10
Motor Iron Loss
L2-02
Momentary power loss ride-through time
L2-03
Momentary power loss Baseblock time
L2-04
Momentary power loss voltage recovery time
L2-05
Uv detection voltage
L3-24
Motor acceleration time
L8-02
Overheat alarm level
L8-09
Ground fault selection
L8-38
Carrier frequency reduction selection
n1-03
Hunting Prevention Time Constant
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Description
Model
Drive Model Selection
Motor Rated Power
B.17 Defaults by Drive Model
Unit
Default Settings
−
BV0006
BV0010
Hex
33
34
kW
1.1
2.2
−
0.5
0.5
–
0.5
0.5
−
7
7
A
6.2
8.5
Hz
2.6
2.9
A
2.8
3
Ω
1.997
1.601
%
18.5
18.4
W
53
77
s
0.2
0.3
s
0.4
0.5
s
0.3
0.3
V dc
160
160
s
0.142
0.145
°C
105
100
−
0
0
−
1
1
ms
10
10
BV0012
BV0018
35
37
3.0
3.7
0.5
0.5
0.5
0.5
7
3
11.4
14.0
2.7
2.73
3.7
4.5
1.034
0.771
19
19.6
91
112
0.5
1.0
0.5
0.6
0.3
0.3
160
160
0.145
0.154
95
100
0
0
1
1
10
10
B
377