5.5 E: Motor Parameters
Setting = C
90 Hz
200
14
7
0
1.5 3
60
90
Frequency (Hz)
Setting a Custom V/f Pattern
Setting parameter E1-03 to "F" allows to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
When E1-03 is changed to "F", the default values for parameters E1-04 to E1-13 will be equal to V/f pattern 1 of the predefined
patterns.
V/f Pattern Settings E1-04 to E1-13
n
Using parameters E1-04 through E1-13, the user can either monitor the V/f pattern values if E1-03 ≤ 15 or set up a custom V/
Figure 5.38
f pattern as shown in
No.
E1-04
E1-05
E1-06
E1-07
E1-08
E1-09
E1-10
E1-11
E1-12
<2>
E1-13
<1> Values shown are for 200 V class drives; double the value when using 400 V class drives.
<2> When E1-13 is set to 0.0 V, the drive uses the value set in E1-05 to control the voltage.
Note:
1. The following condition must be true when setting up the V/f pattern: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
2. Setting E1-11 to 0 disables both E1-11 and E1-12 and the above conditions do not apply.
3. To make the V/f pattern a straight line set E1-09 = E1-07. In this case the E1-08 setting is disregarded.
4. E1-03 is unaffected when the drive is initialized using parameter A1-03, but the settings for E1-04 through E1-13 are returned to their
default values.
158
Table 5.19 Constant Output, Settings C to F
Setting = D
120 Hz
200
14
7
0
1.5 3
60
120
Frequency (Hz)
when E1-03 = F.
Parameter Name
Maximum Output Frequency
Maximum Voltage
Base Frequency
Middle Output Frequency
Middle Output Frequency Voltage
Minimum Output Frequency
Minimum Output Frequency Voltage
Middle Output Frequency 2
Middle Output Frequency Voltage 2
Base Voltage
Output Voltage (V)
Figure 5.38 V/f Pattern
Setting = E
180 Hz
200
14
7
0
1.5 3
60
Frequency (Hz)
0.0 to 255.0 V
0.0 to 255.0 V
0.0 to 255.0 V
0.0 to 255.0 V
Frequency (Hz)
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Setting = F
200
14
7
180
0
1.5 3
Frequency (Hz)
Setting Range
40.0 to 400.0 Hz
<1>
0.0 to E1-04
0.0 to E1-04
<1>
0.0 to E1-04
<1>
0.0 to E1-04
<1>
0.0 to 255.0 Hz
60 Hz
60
Default
60.0 Hz
<1>
230 V
60.0 Hz
3.0 Hz
<1>
18.4 V
1.5 Hz
<1>
13.8 V
0.0 Hz
0.0 V
0.0 V