YASKAWA iQpump Micro CIMR-PW Series User Manual page 56

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

3.7 Control Circuit Wiring
<2> Connect a suppression diode as shown in
circuit voltage.
<3> When set for sourcing. +5 V/1.5 kΩ or higher, +8 V/3.5 kΩ or higher, +10 V/10 kΩ or higher.
<4> When set for sinking, the external power supply should be +12 Vdc, ±5% with 16 mA or less.
A – External power, 48 V max.
B – Suppression diode
Serial Communication Terminals
n
Type
MEMOBUS/Modbus
Communication
Terminal Configuration
u
56
Figure 3.18
when driving a reactive load such as a relay coil. Ensure the diode rating is greater than the
A
Figure 3.18 Connecting a Suppression Diode
Table 3.10 Control Circuit Terminals: Serial Communications
No.
Signal Name
R+
Communications input (+)
R-
Communications input (-)
S+
Communications output (+)
S-
Communications output (-)
IG
Shield ground
R+ R–
S+
S–
IG
P1
P2
PC
A1
A2
+V
AC AM AC MP
MA
MB
MC
S1
S2
S3
S4
S5
S6
S7
HC SC
H1
RP
Figure 3.19 Removable Control Circuit Terminal Block
B
C
D
C – Coil
D – 50 mA or less
MEMOBUS/Modbus communication: Use a
RS-485 or RS-422 cable to connect the drive.
R+ R-
S+
S-
IG
P1
P2
PC
A1
A2
+V
AC AM AC MP
S1
S2
S3
S4
S5
S6
S7
HC SC
H1
RP
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Function (Signal Level)
RS-485/422
MEMOBUS/
Modbus
communication
protocol 115.2 kbps
(max.)
0 V
MA
MB
MC