YASKAWA iQpump Micro CIMR-PW Series User Manual page 439

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

Non-time Delay
Drive Model
Fuse Rating (A)
<1>
2V0040
2V0056
2V0069
4V0002
6
<7>
4V0004
15
<8>
4V0005
20
<9>
4V0007
25
4V0009
25
4V0011
30
4V0018
4V0023
4V0031
4V0038
<1> Maximum 300% of drive input current rating for any Class J, T, or CC fuse except for models 4V0004, 4V0005, and 4V0007.
<2> Maximum 175% of drive input current rating for any Class J, T, or CC fuse.
<3> Maximum 225% of drive input current rating for any Class RK5 fuse.
<4> When using semiconductor fuses, Bussmann FWH are required for UL compliance.
<5> Maximum MCCB Rating is 15 A or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 Vac or greater.
Additionally, when using MCCBs for protection, the drive must be installed in a ventilated enclosure with minimum volume according the "Minimum
Enclosure Volume" column.
<6> Model 4V0004 requires Mersen (Ferraz) part number A6T15 for compliance.
<7> Model 4V0005 requires Mersen (Ferraz) part number A6T20 for compliance.
<8> Model 4V0007 requires Mersen (Ferraz) part number A6T25 for compliance.
Low Voltage Wiring for Control Circuit Terminals
n
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external
power supply shall be a UL-Listed Class 2 power source or equivalent.
Input / Output
Multi-function photocoupler output
Multi-function digital inputs
Multi-function analog inputs
Pulse train input
Pulse train output
Drive Short-Circuit Rating
n
This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current
flow will not rise above 31,000 amps maximum at 240 V for 200 V class drives and 480 V for 400 V class drives.
• The MCCB and breaker protection and fuse ratings shall be equal to or greater than the short-circuit tolerance of the power
supply being used.
• Suitable for use on a circuit capable of delivering not more than 31,000 RMS symmetrical amperes for 240 V in 200 V class
drives (up to 480 V for 400 V class drives) motor overload protection.
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Time Delay Fuses
Class J, T, or CC
Class RK5
Fuse Rating (A)
Fuse Rating (A)
<2>
<3>
90
110
110
150
125
175
400 V Class Three-Phase Drives
3.5
3
7
8
10
10
12
15
15
20
20
30
35
45
40
50
60
80
70
90
Table D.16 Control Circuit Terminal Power Supply
Terminal Signal
P1, P2, PC
S1, S2, S3, S4, S5, S6, S7, SC
A1, A2, AC
RP
MP
Bussmann
Semiconductor
Fuse Part Number
Rating (A)
<4>
(Fuse Ampere)
FWH-200B (200)
FWH-200B (200)
FWH-200B (200)
FWH-40B (40)
FWH-50B (50)
FWH-70B (70)
FWH-70B (70)
FWH-90B (90)
FWH-90B (90)
FWH-80B (80)
FWH-100B (100)
FWH-125B (125)
FWH-200B (200)
Power Supply Specifications
Requires class 2 power supply
Use the internal power supply of the drive. Use class 2 for
external power supply.
Use the internal power supply of the drive. Use class 2 for
external power supply.
Use the internal LVLC power supply of the drive. Use class
2 for external power supply.
Use the internal LVLC power supply of the drive. Use class
2 for external power supply.
D.1 UL Standards
<5>
MCCB
Minimum
Enclosure
3
Volume (in
)
125
1152
150
2560
200
2560
15
1152
15
1152
15
1152
20
1152
20
1152
35
1152
50
1152
60
1152
90
1152
110
1152
439