YASKAWA iQpump Micro CIMR-PW Series User Manual page 336

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

B.8 H Parameters: Multi-Function Terminals
H1-oo
Function
Setting
0
3-Wire sequence
External Reference 1/2
2
Selection
Multi-Step Speed
3
Reference 1
Multi-Step Speed
4
Reference 2
Multi-Step Speed
5
Reference 3
6
Jog reference selection Jog Freq Ref
Accel/decel time
7
selection 1
Baseblock command
8
(N.O.)
Baseblock command
9
(N.C.)
A
Accel/decel ramp hold
Drive overheat alarm
B
(oH2)
Analog terminal input
C
selection
F
Through mode
10
Up command
11
Down command
12
Forward Jog
13
Reverse Jog
14
Fault reset
15
Fast Stop (N.O.)
17
Fast Stop (N.C.)
18
Timer function input
19
PID disable
1B
Program lockout
1E
Reference sample hold Ref Sample Hold
336
Table B.2 H1 Multi-Function Digital Input Selections
LCD Display
Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence)
3-Wire Control
Terminals S1 and S2 are automatically set up for the Run command and Stop
command.
Open: Run command and frequency reference source 1 (determined by b1-01 and
b1-02)
External Ref 1/2 Sel
Closed: Run command and frequency reference source 2 (determined by b1-15
and b1-16)
When input terminals are set to Multi-Step Speed References 1 through 3,
Multi-Step Ref 1
switching combinations of those terminals will create a multi-step speed sequence
using the frequency references set in d1-01 through d1-08.
When input terminals are set to Multi-Step Speed References 1 through 3,
Multi-Step Ref 2
switching combinations of those terminals will create a multi-step speed sequence
using the frequency references set in d1-01 through d1-08.
When input terminals are set to Multi-Step Speed References 1 through 3,
Multi-Step Ref 3
switching combinations of those terminals will create a multi-step speed sequence
using the frequency references set in d1-01 through d1-08.
Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other
reference sources.
Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel
Multi-Acc/Dec 1
time 2
(set in C1-03, C1-04).
Ext BaseBlk N.O.
Closed: No drive output
Ext BaseBlk N.C.
Open: No drive output
Open: Accel/decel is not held
Acc/Dec RampHold
Closed: The drive pauses during acceleration or deceleration and maintains the
output frequency.
OH2 Alarm Signal
Closed: An oH2 alarm occurs
Open: Function assigned by H3-14 is disabled.
Term A2 Enable
Closed: Function assigned by H3-14 is enabled.
Select this setting when using the terminal in a pass-through mode. The terminal
Term Not Used
does not trigger a drive function but can be used as digital input for the controller
the drive is connected to.
The drive accelerates when the Up command terminal closes, and decelerates when
the Down command closes. When both terminals are closed or both are open, the
Up Command 1
drive holds the frequency reference. The Up and Down commands must always
be used in conjunction with one another.
The drive accelerates when the Up command terminal closes, and decelerates when
the Down command closes. When both terminals are closed or both are open, the
Down Command 1
drive holds the frequency reference. The Up and Down commands must always
be used in conjunction with one another.
Forward Jog
Closed: Runs forward at the Jog frequency d1-17.
Reverse Jog
Closed: Runs reverse at the Jog frequency d1-17.
Fault Reset
Closed: Resets faults if the cause is cleared and the Run command is removed.
Fast-Stop N.O.
Closed: Decelerates to stop at the Fast Stop time set to C1-09.
Fast-Stop N.C.
Open: Decelerates to stop at the Fast Stop time set to C1-09.
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction
Timer function
with the timer function output (H2-oo = 12).
Open: PID control enabled
PID Disable
Closed: PID control disabled
Open: Parameters cannot be edited (except for U1-01 if the reference source is
Program Lockout
assigned to the digital operator).
Closed: Parameters can be edited and saved.
Closed: Samples the analog frequency reference and operates the drive at that
speed.
Description
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Page
163
164
164
164
164
164
164
164
164
164
164
165
165
165
165
166
166
166
166
166
167
167
167
167