YASKAWA iQpump Micro CIMR-PW Series User Manual page 403

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

Monitor Data
u
Monitor data can be read only.
Register No.
Drive Status 1
bit 0
bit 1
bit 2
bit 3
bit 4
0020H
bit 5
bit 6
bit 7
bit 8 to bit D
bit E
bit F
Fault Contents 1
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
0021H
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
Data Link Status
bit 0
bit 1
bit 2
0022H
bit 3
bit 4
bit 5
bit 6 to bit F
0023H
Frequency Reference,
0024H
Output Frequency,
0025H
Output Voltage Reference, 0.1 V units (units are determined by parameter H5-10)
0026H
Output Current,
0027H
Output Power
0028H
Torque Reference (OLV only)
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
During Run
During Reverse
Drive Ready
Fault
Data Setting Error
Multi-Function Contact Output (terminal MA/MB-MC)
Multi-Function Photocoupler Output 1 (terminal P1 - PC)
Multi-Function Photocoupler Output 2 (terminal P2 - PC)
Reserved
When ComRef has been enabled
When ComCtrl has been enabled
Overcurrent (oC), Ground fault (GF), IGBT Short Circuit or Ground Fault (SC)
Overvoltage (ov)
Drive Overload (oL2)
Overheat 1 (oH1), Drive Overheat Warning (oH2)
Dynamic Braking Transistor Fault (rr), Braking Resistor Overheat (rH)
Reserved
PID Feedback Loss (FbL/FbH)
EF0 to 7: External Fault
CPFoo: Hardware Fault (includes oFAoo)
Motor Overload (oL1), Overtorque Detection 1/2 (oL3/oL4), Undertorque Detection 1/2 (UL3/
UL4)
Overspeed (oS)
Main Circuit Undervoltage (Uv)
Undervoltage (Uv1), Control Power Supply Undervoltage (Uv2), Soft Charge Circuit Fault (Uv3)
Output Phase Loss (LF), Input Phase Loss (PF)
MEMOBUS/Modbus Communication Error (CE), Option Communication Error (bUS)
Operator Connection Fault (oPr)
Writing data or switching motors
Reserved
Upper or lower limit error
Data conformity error
Writing to EEPROM
Reserved
<1>
<1>
<2>
C.10 MEMOBUS/Modbus Data Table
Contents
C
403