Figure 7.21 Troubleshooting Terminal Board or Control Board Replacement
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Troubleshooting Fault Codes at
Terminal Board (TB) or Control Board (CNT) Replacement
YES
"CPF06" Fault is
displayed upon drive
replacement
Fault "oPE01"
Fault "oPE04"
Initialize the drive using
Parameter A1-03 = 2220 or 3330
START
Note: Drive kVA Setting o2-04 = "FF"
inside a new Terminal Board
NO
YES
NO
Set parameter o2-04 to match drive
nameplate rating
YES
NO
Fault "oPE04" drive parameter settings need
to be initialized or uploaded from the TB
Initialize the drive using
parameter A1-03
Set value = 2220
or 3330
Parameter setting values
are copied
TB to CNT
Ready
END
7.5 Drive Replacement
Set value = 5550
7
305