YASKAWA iQpump Micro CIMR-PW Series User Manual page 237

Ac drive compact intelligent pump controller
Table of Contents

Advertisement

Minimum pump speed and thrust speed are disregarded during Anti-Jam operation. The pre-charge timer is held and will not
increment during anti-jam or de-scale operations.
P7-01: Anti-Jam Operation Selection
n
Enables and disables the Anti-Jam function.
No.
P7-01
Setting 0: Disabled
Setting 1: Enabled
P7-02: Anti-Jam Cycle Count
n
Sets the maximum number of cycle attempts before the Anti-Jam fault occurs.
No.
P7-02
P7-03: Anti-Jam Detection Current Level
n
Sets the current level (at start) that will trigger the Anti-Jam function. Set as a percentage of motor rated current.
No.
P7-03
P7-04: Anti-Jam Detection Time at Start
n
Sets the amount of time the current must be above the level set in P7-03 to trigger the Anti-Jam function.
No.
P7-04
P7-05: Anti-Jam During Run Current
n
Sets the current level (during run) that will trigger the Anti-Jam function. Set as a percentage of motor rated current.
A setting of 0% disables Anti-Jam during run.
No.
P7-05
P7-06: Anti-Jam During Run Time
n
Sets the amount of time that the current must be above the level set in P7-05 to trigger the Anti-Jam function.
No.
P7-06
P7-07: Anti-Jam Frequency Reference
n
Sets the maximum speed when the Anti-Jam feature is operating.
No.
P7-07
P7-08: Anti-Jam Release Time
n
Sets the amount of time that the current must fall below the level set in P7-03 to resume normal operation.
No.
P7-08
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Name
Anti-Jam Operation Selection
Name
Anti-Jam Cycle Count
Name
Anti-Jam Detection Current Level
Name
Anti-Jam Detection Time at Start
Name
Anti-Jam During Run Current
Name
Anti-Jam During Run Time
Name
Anti-Jam Frequency Reference
Name
Anti-Jam Release Time
5.11 P: Pump
Setting Range
0, 1
Setting Range
1 to 100
Setting Range
50 to 200%
Setting Range
0.1 to 2.0
Setting Range
0 to 200%
Setting Range
0.1 to 2.0 s
Setting Range
0.00 to 400.00 Hz
Setting Range
0.5 to 10.0 s
Default
0
Default
1
Default
120%
Default
0.3 s
Default
0%
Default
0.3 s
5
Default
25.00 Hz
Default
2.0 s
237

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents