5.8 L: Protection Functions
Overload Tolerance
150
Rated Speed=100% Speed
60 sec.
100
55
50
Continuous
0
110
100120 167 200
(60 Hz)
Speed (%)
Setting 3: Vector Motor (constant torque, 1:100)
Use this setting when operating a drive dedicated motor with a torque ratio of 1:100. This motor type is allowed to run with
100% load from 1% up to 100% speed. Running slower speeds with full load can trigger an overload fault.
Overload Tolerance
150
Rated Speed=100% Speed
60 sec.
100
90
Continuous
50
0 1
100120 167 200
(60 Hz)
Speed (%)
Setting 6: General-Purpose Motor
Note:
General-purpose motors are designed with a base speed that operates at line frequency (50/60 Hz depending on geographic region).
Because the motor is self-cooled, the overload tolerance drops when the motor speed is lowered. The drive appropriately
adjusts the electrothermal trigger point according to the motor overload characteristics and protects the motor from overheat
throughout the entire speed range.
Overload Tolerance
150
Rated Speed=100% Speed
60 s
A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
C: Max. speed for 132MJ and below
100
90
60
Continuous
50
A
B
05 33
100 120 167 200
Speed (%)
L1-02: Motor Overload Protection Time
n
Sets the time for the drive to shut down on motor overload (oL1) when the motor is running with excessive current. Enter the
time the motor can withstand operating at 150% current after previously running at 100% current (hot motor overload
condition). This parameter rarely requires adjustment.
No.
L1-02
190
A
D
B
A
B
D
C
Name
Motor Overload Protection Time
Cooling Ability
Motor is designed to effectively cool
itself at speeds as low as 6 Hz.
Cooling Ability
Motor is designed to effectively cool
itself at speeds as low as approximately
0.6 Hz.
Cooling Ability
Motor designed to operate from line
power. Motor cooling is most effective
when running at rated base frequency
(check the motor nameplate or
specifications)
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Overload Characteristics
Continuous operation with 100% load
from 6 Hz to 50/60 Hz.
Overload Characteristics
Continuous operation with 100% load
from 0.6 Hz to 50/60 Hz.
Overload Characteristics
Continuous operation at less than line
power frequency with 100% load can
trigger motor overload protection
(oL1). A fault is output and the motor
will coast to stop.
Setting Range
0.1 to 5.0 minutes
Default
1.0 minutes