5.10 o: Operator Related Settings
No.
o2-02
Setting 0: Disabled
The STOP key has no function when the drive is controlled by a source other than the digital operator. The drive can only be
stopped from the Run command source that has been selected.
Setting 1: Enabled
The STOP key can be used to terminate the operation, even if the Run command source is not assigned to the digital operator.
If operation has been interrupted by pressing the STOP key, the Run command must be cycled to restart the drive.
o2-03: User Parameter Default Value
n
Once drive parameters are set up completely, the values set can be saved as "User Initialization Values" by setting parameter
o2-03. Once this has been done, the "Initialize Parameters" parameter (A1-03) will offer the choice of "1110: User Initialize".
Choosing A1-03 = "1110: User Initialize", will reset all parameters to the values saved as "User Initialization Values".
No.
o2-03
Setting 0: No Change
All "User Initialization Values" are saved as they are.
Setting 1: Set User Initialization Values
The current parameter settings are saved as "User Initialization Values". After setting o2-03 to 1 and pressing the ENTER
key, the values are saved and the display returns to 0.
Setting 2: Clear User Initialization Values
All "User Initialization Values" are cleared. After setting o2-03 to 2 and pressing the ENTER key, the values are erased and
the display returns to 0. A1-03 = 1110 becomes invalid.
o2-04: Drive Model Selection
n
Parameter o2-04 matches the control board to the drive hardware. Proper setting of o2-04 is important for optimal performance
and proper protection for the drive hardware. This parameter is configured at the factory and does not normally require
adjustment in the field. It is available primarily to accommodate control board replacement in the event of damage.
No.
o2-04
Note:
1.
Refer to Defaults by Drive Model on page 377
selection.
2. Drive performance will suffer if the correct drive capacity is not set to o2-04, and protective functions will fail to operate properly.
3. This parameter is not reset to the default value when the drive is initialized using A1-03.
o2-05: Frequency Reference Setting Method Selection
n
Determines if the ENTER key must be used to input a frequency reference from the digital operator.
No.
o2-05
Setting 0: ENTER Key Required
Every change in the frequency reference setting on the digital operator has to be finalized by pressing the ENTER key before
it becomes effective.
Setting 1: ENTER Key Not Required
The output frequency changes immediately when the reference is changed by the UP and DOWN key on the digital operator.
The ENTER key does not need to be pressed. The frequency reference is saved five seconds after the Up or DOWN key has
been released. If an undervoltage error (Uv) occurs within 5 seconds of pressing the ENTER key, the frequency reference will
not be saved to memory. The digital operator display flashes when settings can be made to the frequency reference.
218
Name
STOP Key Function Selection
Name
User Parameter Default Value
Name
Drive Model Selection
Name
Frequency Reference Setting Method Selection
for a list of o2-04 settings and parameters that change depending on the drive model
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Setting Range
0 or 1
Setting Range
0 to 2
Setting Range
Depending on drive
-
Setting Range
0 or 1
Default
1
Default
0
Default
size
Default
0