L5-40: Low Feedback Fault Retry Selection
n
No.
L5-40
Setting 0: No retry
Setting 1: Retry
L5-41: High Feedback Fault Retry Selection
n
No.
L5-41
Setting 0: No retry
Setting 1: Retry
L5-42: Feedback Loss Fault Retry Selection
n
No.
L5-42
Setting 0: No retry
Setting 1: Retry
L5-50: Setpoint Not Met Retry Selection
n
No.
L5-50
Setting 0: No retry
Setting 1: Retry
L5-51: Loss of Prime Fault Retry Selection
n
No.
L5-51
Setting 0: No retry
Setting 1: Retry
L5-52: Pump Over Cycle Fault Retry Selection
n
No.
L5-52
Setting 0: No retry
Setting 1: Retry
L5-53: Volute-Thermostat Retry Selection
n
No.
L5-53
Volute Thermostat Digital Inputs
n
There are two multi-function digital input settings, one normally open (closed causes the fault) and one normally closed (open
causes the fault). Only one of these inputs may be programmed into the H1-oo parameters at a time.
Setting 0: No retry
Setting 1: Retry
When automatic retries are enabled (L5-01 > 0) and the drive faults on FLTS – Volute-TStat Flt , the drive will wait for the
Volute-Thermostat digital input to deactivate plus the L5-04 time before the drive will restart.
L6: Torque Detection
u
The drive provides two independent torque detection functions that trigger an alarm or fault signal when the load is too heavy
(oL), or suddenly drops (UL). They are set up using the L6-oo parameters. To indicate the underload or overload condition
to an external device, digital outputs should be programmed as shown below.
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Name
Low Feedback Fault Retry Selection
Name
High Feedback Fault Retry Selection
Name
Feedback Loss Fault Retry Selection
Name
Setpoint Not Met Retry Selection
Name
Loss of Prime Fault Retry Selection
Name
Pump Over Cycle Fault Retry Selection
Name
Volute-Thermostat Retry Selection
5.8 L: Protection Functions
Setting Range
0, 1
Setting Range
0, 1
Setting Range
0, 1
Setting Range
0, 1
Setting Range
0, 1
Setting Range
0, 1
Setting Range
0, 1
Default
0
Default
0
Default
0
Default
0
Default
0
Default
0
Default