4.8 iQpump Presets and Functions
Setting the Drive Networking Parameters
1.
1. Set parameter H5-01, Serial Node Address, on each drive.
Note:
For optimal performance, use consecutive numbers starting from 1. Parameter setting H5-01 must be unique for each drive.
2.
Set parameter P9-25, Highest Node Address, on each drive.
Note:
For optimal performance, set to highest H5-01 value. This setting must be the same for all the drives on the network.
3.
Set P1-01 to 3 (MEMOBUS/Modbus Network) on all the drives.
4.
Cycle main power to all networked drives.
Note:
The H5-01 setting will not take effect until power is cycled to the drive and may cause communication errors and unexpected
behavior.
Verifying Drive Network Communications
Access monitor U9-02, Network Activity, and verify:
• No drives have a value of 0 <->
• All drives are receiving valid data indicated by a regular change in the monitor value.
• At least one drive has the unit <M>, while the others have the unit <+>.
Network State
Drive is the Master and is
communicating with
another drive.
Drive is a node on the
network and is
communicating with a
Master.
Drive is not able to
communicate to any other
drives.
If a drive displays U9-02 = 0 <->:
94
Drive 1
R+
R-
S +
S-
Figure 4.13 Daisy Chain Three Drives
Table 4.9 Network Connectivity Information
Top Line on Home Screen
(o1-12 = 1)
<M> CONNECTED
Pump Off Network
U5-99=
100.0
U1-02=
0.00Hz
U1-91=
62.8PSI
<- MONITOR - >
<+> CONNECTED
Pump Off Network
U5-99=
100.0
U1-02=
0.00Hz
U1-91=
62.8PSI
<- MONITOR - >
<-> DISCONNECTED
Pump Off Network
U5-99=
100.0
U1-02=
0.00Hz
U1-91=
62.8PSI
<- MONITOR - >
Drive 2
R+
R-
S+
S-
PSI
PSI
PSI
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Drive 3
R+
R-
S+
S-
U9-02 Network Activity
- MONITR -
DRV RDY
Network Activity
U9-02=
9453
U1-02=
0.00Hz
U1-91=
62.8PSI
Home
FWD
- MONITR -
DRV RDY
Network Activity
U9-02=
324
U1-02=
0.00Hz
U1-91=
62.8PSI
FWD
Home
- MONITR -
DRV RDY
Network Activity
U9-02=
U1-02=
0.00Hz
U1-91=
62.8PSI
FWD
Home
<M>
<+>
0
<->

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents