A.2 Drive Specifications
Item
Heatsink Overheat Protection
Braking Resistor Overheat Protection Overheat input signal for braking resistor (Optional ERF-type, 3% ED)
Stall Prevention
Protection
Functions
Cooling Fan Failure Protection
Ground Fault Protection
DC Bus Charge LED
Storage/Installation Area
Ambient Temperature
Storage Temperature
Shock, Impact
Environment
Surrounding Area
Standards
Protective Enclosure
Cooling Method
<1> Instantaneous average deceleration torque refers to the torque required to decelerate the motor (uncoupled from the load) from the rated motor speed
down to zero in the shortest time.
<2> Ensure that Stall Prevention Selection during Deceleration is disabled (L3-04 = 0) or set to 3 when using a braking resistor or the Braking Resistor
Unit. The default setting for the stall prevention function will interfere with the braking resistor.
<3> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<4> A Momentary Power Loss Ride-Thru Unit is required for 200/400 V class drives 7.5 kW and less if the application needs to continue running during
a momentary power loss up to 2 seconds.
<5> Ground protection cannot be provided under the following circumstances when a ground fault is likely in the motor windings during run: Low
ground resistance for the motor cable and terminal block; low ground resistance for the motor cable and terminal block; or the drive is powered up
from a ground short.
312
Protected by thermistor
Stall prevention is available during acceleration, deceleration, and during run. Separate
settings for each type of stall prevention determine the current level at which stall prevention
is triggered.
Circuit protection ("fan-lock" sensor)
Electronic circuit protection
Remains lit until DC bus voltage falls below 50 V
Indoors
IP20/NEMA 1, UL Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F)
IP66/NEMA 4X, UL Type 4X enclosure: -10 °C to +40 °C (14 °F to 104 °F)
Humidity
95% RH or less with no condensation
-20 to +60 °C (-4 to +140 °F) allowed for short-term transport of the product
Up to 1000 meters without derating; up to 3000 meters with output current and voltage
Altitude
derating.
10 to 20 Hz: 9.8 m/s
20 to 55 Hz: 5.9 m/s
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
For IP66/NEMA 4X, UL Type 4X enclosure drives, install the drive in an environment suitable
for IP66/NEMA 4X, UL Type 4X enclosures:
• NEMA 4X, UL Type 4X – Enclosures constructed for either indoor or outdoor use to
provide a degree of protection to personnel against incidental contact with the enclosed
equipment; to provide a degree of protection against falling dirt, rain, sleet, snow,
windblown dust, splashing water, hose-directed water, and corrosion; and that will be
undamaged by the external formation of ice on the enclosure.
• IP66 – Dust-tight enclosures to not allow any dust to penetrate. The enclosure guards the
drive against powerful jetting water sprayed from any direction and is protected against
access to hazardous parts with a wire.
Orientation
Install the drive vertically to maintain maximum cooling effects
cULus
IP20/NEMA 1, UL Type 1
IP66/NEMA 4X, UL Type 4X
BV0006F: self-cooled
BV0010F to BV0018F: cooling fan
2V0006F to 2V0069F: cooling fan
4V0002F to 4V0004F: self-cooled
4V0005F to 4V0038F: cooling fan
Specification
<5>
2
2
BV0006G and BV0010G: self-cooled
BV0012G: internal cooling fan
2V0006G to 2V0012G: self-cooled
2V0020G: internal cooling fan
2V0030G to 2V0069G: internal and external
cooling fans
4V0002G to 4V0005G: self-cooled
4V0007G to 4V0011G: internal cooling fan
4V0018G to 4V0038G: internal and external
cooling fans
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual