5.11 P: Pump
P4-23: Low City Off-Delay Time
n
Sets the amount of time a "Low City Pressure" condition must be absent before the drive will restart.
No.
P4-23
P4-24: Low City Alarm Text
n
Selects the alarm message that will be displayed when a "Low City Pressure" condition is detected.
No.
P4-24
Setting 0: Low city pressure
Setting 1: Low suction pressure
Setting 2: Low water in tank
P4-25: Remote Drive Disable Selection
n
No.
P4-25
Setting 0: Normally open
When this parameter is set to 0 and digital input H1-0o = 95 (Remote Drive Disable) is closed for the time set in P4-26, Drive
Disable On-Delay, the drive will stop according to the method set in b1-03.
The drive will not run, and will display the "R-DNE-Sx" alarm where "Sx" denotes the digital input terminal programmed for
this function. For example, if H1-03 = 95, the alarm will display: "R-DNE-S3".
To be able to run again, the Remote Drive Disable digital input has to be opened for the time set in P4-27, Drive Disable Off-
Delay.
Setting 1: Normally closed
When this parameter is set to 0 and digital input H1-0o = 95 (Remote Drive Disable) is opened for the time set in P4-26,
Drive Disable On-Delay, the drive will stop according to the method set in b1-03.
When drive run is disabled using this feature, the Pre-Charge function is reset and will run if necessary when drive run is
enabled.
P4-26: Remote Drive Disable On-Delay
n
Sets the amount of time a "Remote Drive Disable" condition must be present before the drive will stop.
No.
P4-26
P4-27: Remote Drive Disable Off-Delay
n
Sets the amount of time a "Remote Drive Disable" condition must be absent before the drive will be allowed to restart.
No.
P4-27
P4-29: Lube Pump Message Text
n
Selects which text is displayed when Lube Pump is active. Also changes the text for the Lube Pump Digital Output selection
(H2-oo = 8B)
No.
P4-29
Setting 0: Lube Pump
Setting 1: Digital Out Delay
P4-30: Lube Pump Active During Run
n
When enabled, the Lube Pump digital output stays activated after the timer expires and the drive starts to run normally. The
output is deactivated only when the drive stops, faults, or sleeps.
234
Name
Low City Input Off-Delay Time
Name
Low City Alarm Text
Name
Remote Drive Disable Selection
Name
Remote Drive Disable On-Delay
Name
Remote Drive Disable Off-Delay
Name
Lube Pump Message Text
Setting Range
1 to 1000 s
Setting Range
Setting Range
Setting Range
0 to 1000 s
Setting Range
0 to 1000 s
Setting Range
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Default
5 s
Default
0 to 2
Default
0, 1
Default
0 s
Default
0 s
Default
0, 1
0
1
0