C.5 MEMOBUS/Modbus Setup Parameters
H5-11: Communications Enter Function Selection
n
Selects if an Enter command is needed to change parameter values via MEMOBUS/Modbus communications.
Command on page
415.
No.
H5-11
Setting 0: Enter command necessary
Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter
change, not for each single parameter.
Setting 1: Enter command not necessary
Parameter value changes become effective immediately without the need to send an Enter command.
H5-12: Run Command Method Selection
n
Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications
(b1-02/16 = 2).
No.
H5-12
Setting 0: FWD/Stop, REV/Stop
Bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive in the forward direction. Bit 1 will start and stop the
drive in reverse.
Setting 1: Run/Stop, FWD/REV
Bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive. Bit 1 changes the direction.
394
Name
Communications Enter Function Selection
Name
Run Command Method Selection
Setting Range
Setting Range
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Refer to Enter
Default
0 or 1
Default
0 or 1
0
0