3.6 Main Circuit Wiring
Drive
Model
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
, 1, 2
2V0056
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
, 1, 2
2V0069
B1, B2
Three-Phase 400 V Class
n
Drive
Model
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4V0002
, 1, 2
4V0004
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4V0005
, 1, 2
4V0007
4V0009
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
, 1, 2
4V0011
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
, 1, 2
4V0018
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
, 1, 2
4V0023
B1, B2
52
Terminal
Table 3.6 Wire Gauge and Torque Specifications
Terminal
Recomm.
Wire Range
Gauge
AWG, kcmil
AWG, kcmil
4
6 to 4
4
6 to 4
–
6 to 4
–
10 to 6
6
8 to 4
3
8 to 2
3
8 to 2
–
8 to 2
–
8 to 6
6
6 to 4
Recomm.
Wire Range
Gauge
AWG, kcmil
AWG, kcmil
14
14 to 10
14
14 to 10
–
14 to 10
–
14 to 10
14
14 to 10
14
14 to 10
14
14 to 10
–
14 to 10
–
14 to 10
10
14 to 10
12
14 to 10
14
14 to 10
–
14 to 10
–
14 to 10
10
14 to 10
10
14 to 6
10
14 to 6
–
14 to 6
–
14 to 10
8
14 to 6
10
10 to 6
10
10 to 6
–
10 to 6
–
14 to 10
8
10 to 6
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Tightening
Screw
Torque
Size
N•m (lb.in.)
5.4 to 6.0
M6
(47.8 to 53.1)
2.7 to 3.0
M5
(23.9 to 26.6)
5.4 to 6.0
M6
(47.8 to 53.1)
9.9 to 11
M8
(87.6 to 97.4)
2.7 to 3.0
M5
(23.9 to 26.6)
5.4 to 6.0
M6
(47.8 to 53.1)
Tightening
Screw
Torque
Size
N•m (lb.in.)
1.2 to 1.5
M4
(10.6 to 13.3)
1.2 to 1.5
M4
(10.6 to 13.3)
1.2 to 1.5
M4
(10.6 to 13.3)
2.1 to 2.3
M4
(18.6 to 20.4)
2 to 2.5
M5
(17.7 to 22.1)
2.1 to 2.3
M4
(18.6 to 20.4)
2 to 2.5
M5
(17.7 to 22.1)