5.10 o: Operator Related Settings
3: OP<-->INV VERIFY
Parameter settings in the drive are compared to those in the digital operator.
Note:
When using the copy function, the drive model number (o2-04) and the software number (U1-14) must match or an error will occur.
o3-02 Copy Allowed Selection
n
Enables and disables the digital operator copy functions.
No.
o3-02
0: Disabled
No digital operator copy functions are allowed
1: Enabled
Copying allowed
o4: Maintenance Monitor Settings
u
o4-01: Accumulated Operation Time Setting
n
Parameter o4-01 sets the cumulative operation time and allows the user to set the starting value of the accumulated operation
time displayed in monitor U4-01.
Note:
The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will also
be displayed in monitor U4-01.
No.
o4-01
o4-02: Accumulated Operation Time Selection
n
Selects the conditions for what is to be considered "accumulated operation time." Accumulated operation time is displayed in
U4-01.
No.
o4-02
Setting 0: Power On Time
The drive logs the time it is connected to a power supply, no matter if the motor is running or not.
Setting 1: Run Time
The drive logs the time that the output is active, i.e., whenever a Run command is active (even if the motor is not rotating) or
a voltage is output.
o4-03: Cooling Fan Operation Time/Maintenance Setting
n
Sets the value of the cooling fan operation time counter displayed in monitor U4-03. Parameter o4-03 also sets the base value
used for the cooling fan maintenance value displayed in U4-04. Be sure to reset this parameter back to 0 if the cooling fan is
replaced.
Note:
1. The value in o4-03 is set in 10 h units. For example, a setting of 30 will set the cooling fan operation time counter to 300 h. "300" will
be displayed in monitor U4-03.
2. The actual maintenance time depends on the environment the drive is used in.
No.
o4-03
o4-05: Capacitor Maintenance Setting
n
Sets value of the maintenance monitor for the DC bus capacitors displayed in U4-05 as a percentage of the total expected
performance life. This value should be reset to 0 when the DC bus capacitors have been replaced.
Note:
The actual maintenance time will depend on the environment the drive is used in.
No.
o4-05
220
Name
Copy Allowed Selection
Name
Accumulated Operation Time Setting
Name
Accumulated Operation Time Selection
Name
Cooling Fan Operation Time
Name
Capacitor Maintenance Setting
Setting Range
Setting Range
0 to 9999
Setting Range
Setting Range
0 to 9999
Setting Range
0 to 150%
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Default
0, 1
Default
Default
0 or 1
Default
Default
0%
0
0
0
0