Three-Phase 200 V Class Drives
u
Item
Three-Phase Drive Model
Maximum Motor Size Allowed kW (HP)
Input
Rated Output Capacity (kVA)
Output
Max Output Voltage (V)
Max Output Frequency (Hz)
Power Supply
Allowable Voltage Fluctuation
Harmonic Corrective
Actions
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor rated current.
<2> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 230 V.
<4> DC is not available for UL standards.
Item
Three-Phase Model
Maximum Motor Size Allowed kW (HP)
Input
Rated Output Capacity (kVA)
Output
Max Output Frequency (Hz)
Power Supply
Allowable Voltage Fluctuation
Harmonic Corrective
Actions
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor rated current.
<2> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 230 V.
<4> DC is not available for UL standards.
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Table A.2 Three-Phase 200 V Class Power Ratings
<1>
<2>
Input Current (A)
<3>
Output Current (A)
Overload Tolerance
Carrier Frequency
Rated Voltage
Rated Frequency
Allowable Frequency
Fluctuation
DC Link Choke
Table A.3 Three-Phase 200 V Class Power Ratings Continued
<1>
<2>
Input Current (A)
<3>
Output Current (A)
Overload Tolerance
Carrier Frequency
Max Output Voltage (V)
Rated Voltage
Rated Frequency
Allowable Frequency
Fluctuation
DC Link Choke
Specification
2V0006
2V0010
1.1 (1.5)
2.2 (3)
7.3
10.8
2.3
3.7
6.0
9.6
120% of rated output current for 1 minute
(Derating may be required for applications that start and stop frequently)
User-adjustable 2 to 15 kHz
Three-phase power: 200 to 240 V
(proportional to input voltage)
400 Hz (user-adjustable)
Three-phase power: 200 to 240 V 50/60 Hz
DC power supply: 270 to 340 V
Specification
2V0030
2V0040
7.5 (10)
11 (10)
37.0
52.0
11.4
15.2
30.0
40.0
120% of rated output current for 1 minute
(Derating may be required for applications that start and stop frequently)
User-adjustable 2 to 15 kHz
Three-phase power: 200 to 240 V
(proportional to input voltage)
400 Hz (user-adjustable)
Three-phase power: 200 to 240 V 50/60 Hz
DC power supply: 270 to 340 V
A.1 Power Ratings
2V0012
3.0 (3)
13.9
4.6
12.0
<4>
-15 to 10%
±5%
Optional
2V0056
15 (20)
68.0
21.3
56.0
<4>
-15 to 10%
±5%
Optional
2V0020
5.5 (5)
24.0
7.5
19.6
2V0069
18.5 (25)
80.0
26.3
69.0