B.13 Q: PID Controller Parameters
B.13 Q: PID Controller Parameters
Q1: Preset Setpoint
u
No.
(Addr.
Name
Hex)
Q1-01
(0E58)
PID Controller Setpoint 1 Setpoint 1
Q1-02
(0E59)
PID Controller Setpoint 2 Setpoint 2
Q1-03
(0E5A) PID Controller Setpoint 3 Setpoint 3
Q1-04
(0E5B) PID Controller Setpoint 4 Setpoint 4
Q1-09
PID Setpoint Set via Motor
(0E60)
Operated Pot
<1> Unit is determined by P1-02, System Units; scaling is determined by P1-03, Feedback Device Scaling; resolution is determined by b5-39, PID
System Units Display Digits.
u
Q3: Output Current Limit
No.
(Addr.
Name
Hex)
Q3-01
Output Current Limit
(0EBC)
Select
Q3-02
Current Limit
(0EBD)
Q3-10
Ripple Regulator
(0EC5)
Selection
Q3-11
Ripple Regulator
(0EC6)
Setpoint
366
LCD Display
Sets the PID Setpoint when b1-01 is set to 0.
Sets the PID Setpoint when the "Multi Setpoint 1" or
"Alternate Multi Setpoint 1" multi-function digital input is
closed.
Sets the PID Setpoint when the "Multi Setpoint 2" or
"Alternate Multi Setpoint 2" digital input is closed.
Sets the PID Setpoint when the "Multi Setpoint 1" and "Multi
Setpoint 2" or "Alternate Multi Setpoint 3" multi-function
digital inputs are closed.
Selects whether parameters Q1-01 to Q1-04 are changed via
Setpoint MOP
MOP from the home screen.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
LCD Display
Current Lim Sel
Enables and disables the output current regulator.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Sets the current limit. Value is internally limited to 300% of the
Current Limit
drive rated current.
Ripple Reg Sel
Enables and disables the single phase ripple regulator.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
2: Enabled(Reactor)
2: Enabled w/ Line Reactor
Set as a percentage of the maximum amount of ripple allowed
Ripple Reg S.P.
before triggering an input phase loss fault.
Description
Description
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Values
Page
Default: 0.0
Min.: 0.0
245
Max.: 6000.0
<1>
Default: 0.0
Min.: 0.0
245
Max.: 6000.0
<1>
Default: 0.0
Min.: 0.0
245
Max.: 6000.0
<1>
Default: 0.0
Min.: 0.0
245
Max.: 6000.0
<1>
Default: 0
245
Range: 0, 1
Values
Page
Default: 0
245
Range: 0, 1
Default: 0.0 A
245
Min.: 0.0
Max.: 1000.0
Default: 1
245
Range: 0 to 2
Default: 95.0%
Min.: 0.0
245
Max.: 200.0